Technical data – IDEC FL1E SmartRelay User Manual

Page 312

Advertising
background image

Technical data

298

IDEC SmartRelay Manual

Note: Use a surge absorber, noise cut transformer, or noise filter to protect products

rated at 12/24V DC or 24V DC power type modules against surge.

Electromagnetic compatibility (EMC)
Noise emission

EN 55011/A

EN 55022/B
EN 50081-1

(domestic area)

Limit class B group 1

Electrostatic discharge

IEC 61000-4-2
Severity 3

8 kV air discharge
6 kV contact discharge

Electromagnetic fields

IEC 61000-4-3

Field strength 1 V/m and 10
V/m

HF currents on cables and
cable shielding

IEC 61000-4-6

10 V

Burst pulses

IEC 61000-4-4

Severity 3

2 kV (supply and signal
lines)

High-energy surge pulse
(applies only to

FL1E-H12RCC/

FL1E-B12RCC)

IEC 61000-4-5

Severity 3

1 kV (power lines)
symmetrical
2 kV (power lines)
asymmetrical

Safety to IEC
Clearance and creepage
distance rating

IEC 60664, IEC 61131-2,
EN 50178

cULus to UL 508, CSA
C22.2 No. 142

With FL1E-H12RCC/
FL1E-B12RCC, also
IEC60730-1

Fulfilled

Insulation strength

IEC 61131-2

Fulfilled

Cycle time
Cycle time per function

< 0.1 ms

Startup
Startup time at power-up

typ. 9 s

Criterion

Tested in accordance with Values