IDEC FL1E SmartRelay User Manual

Page 336

Advertising
background image

Determining the cycle time

322

IDEC SmartRelay Manual

Test program

1. Create the test program by linking an output to a

frequency trigger and connecting the trigger input with an

inverted marker.

Par

Qx

B1

M1

M1

M1

1

B2

Output Qx or other marker Mx

2. Configure the frequency trigger as shown below. A pulse

is generated in each program cycle due to the inverted

marker. The trigger interval is set to 2 seconds.

B1 1+
On =1000
Off=0000

B1 2
G_T=02:00s

Press

3. Now start the circuit program and switch IDEC

SmartRelay to parameter assignment mode. In this

mode, view the trigger parameters.

B1
On

=1000

Off =0000
fa

=2130

f

a

= total of measured pulses per

timebase G_T

4. The reciprocal value of f

a

is equivalent to the IDEC

SmartRelay execution time of the current circuit program

in its memory.
1/f

a

= cycle time in s

Advertising