Technical data – IDEC FL1E SmartRelay User Manual

Page 320

Advertising
background image

Technical data

306

IDEC SmartRelay Manual

(1): When FL1E-H12SND or FL1B-M08B1S2 are switched on, signal 1 is sent to the

digital outputs for about 50 microseconds. Take this into account, especially when
using devices that react to short pulses.

(2) The maximum switching rate is only dependent on the switching program’s cycle

time.

Line length (shielded and twisted)

10 m

Error limit

+/- 1.5% at full scale

Digital outputs
Number

4

Output type

Transistor, current-sourcing

(1)

Electrical isolation

No

In groups of
Control of a digital input

Yes

Output voltage

Supply voltage

Output current

max. 0.3 A

Short circuit-proof and overload-proof

Yes

Short circuit current limitation

Approx. 1 A

Derating

none; across the entire temperature range

Short circuit-proof cos 1

not applicable for this module

Short circuit-proof cos 0.5 to 0.7

not applicable for this module

Parallel output circuit for power increase

Not permitted

Protection of output relay (if desired)
Switching rate

(2)

Mechanical

not applicable for this module

Electrical

10 Hz

Ohmic load/lamp load

10 Hz

Inductive load

0.5 Hz

FL1E-H12SND

=

<