4.4.18 Analog comparator

Short description

The output is set and reset depending on the difference Ax -

Ay and on two configurable thresholds.

Gain and offset parameters

For more information on the gain and offset parameters,

refer to Chapter 4.3.6.

Parameters On and Off

The on threshold On and the off threshold Off can be

provided by the actual value of another already-programmed

function. You can use the actual values of the following

functions:

• Analog comparator (actual value Ax - Ay, see Chapter

4.4.18)

• Analog trigger (actual value Ax, see Chapter 4.4.16)

• Analog amplifier (actual value Ax, see Chapter 4.4.20)

• Analog multiplexer (actual value AQ, see Chapter 4.4.26)

• Analog ramp control (actual value AQ, see Chapter

4.4.27)

• Analog math (actual value AQ, see Chapter 4.4.30)

• PI controller (actual value AQ, see Chapter 4.4.28)

• Up/down counter (actual value Cnt, see Chapter 4.4.13)

Select the required function by the block number.

Symbol in IDEC

SmartRelay

Wiring

Description

Inputs Ax
and Ay

You apply the analog signals the
difference of which you want to
analyze at the inputs Ax and Ay.
Use the analog inputs AI1...AI8

(

*

)

, the

analog memory markers AM1...AM6,
the block number of a function with
analog output, or the analog outputs
AQ1 and AQ2.

Parameter A: Gain

Range of values:

10.00

B: Zero offset Range of values:

10,000

On: On threshold

Range of values:

20,000

Off: Off threshold

Range of values:

20,000

p: Number of decimals

Range of values: 0, 1, 2, 3

Output Q

Q is set or reset, depending on the
difference Ax - Ay and the set
thresholds.

* AI1...AI8: 0...10 V corresponds with 0...1000 (internal value).