Applications, Idec smartrelay manual 277 – IDEC FL1E SmartRelay User Manual

Page 291

Advertising
background image

Applications

IDEC SmartRelay Manual

277

The circuit diagram for conventional solutions is as follows:

K1

K5

K5

S1

S0

K3

K2

L1

N

S2

K1

v>

S2

H1

K4

S3 v>

K5

H2

K2

K4

Auxiliary circuit

Exhaust air

Fresh air

Operation

Error

The fans are monitored by means of flow sensors. If no air

flow is registered within a short waiting time, the system is

switched off and an error message is output. This message

can be acknowledged by pressing the OFF button.
In addition to the flow sensors, the fan monitoring system

also requires an evaluating circuit with several switching

devices. This evaluating circuit can be replaced by a single

IDEC SmartRelay unit.

Wiring of an air-conditioning system with FL1E-H12RCC

L1 N

I1

I3 I6 I7 I8

Q1

Q2

Q3

Q4

K1

K2

S1

L1

N

S2

S3 v>

v>

H1

H2

S0

I4

I5

I1 I2 I3

I1 I2 I3

1 2

1 2 1 2 1 2

Exhaust

fan

Fresh-air
fan