Technical data

310

IDEC SmartRelay Manual

Digital inputs
Number

8,

optional P action or N action

Electrical isolation

No

High speed inputs

not applicable for this module

Input frequency
• Normal input
• High speed input

• max. 4 Hz
• not applicable for this module

Input voltage
• Signal 0
• Signal 1

L
< 5 V AC/DC
> 12 V AC/DC

Input current at
• Signal 0
• Signal 1

< 1.0 mA
> 2.5 mA

Delay time at
• 0 to 1
• 1 to 0

typ. 1.5 ms
typ. 15 ms

Line length (unshielded)

100 m

Analog inputs
Number
Range
max. Input voltage
Digital outputs
Number

4

Output type

Relay outputs

Electrical isolation

Yes

Dielectric Strength (between power/input
terminals and output terminals)

2,500 V AC, 1minute
500 V DC, 1 minute

In groups of

1

Control of a digital input

Yes

Continuous current I

th

max. 10 A per relay

Surge current

max. 30 A

Incandescent lamp load

(25000 switching cycles) at

1000 W

Fluorescent tubes with ballast

(25000 switching cycles)

10 x 58 W

Fluorescent tubes, conventionally
compensated (25000 switching cycles)

1 x 58 W

FL1E-H12RCA

FL1E-B12RCA