MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

101

Master Programming Level

Programming

The Canadian Options configures the FACP with the following as required by Canada:

The following monitor module type codes are not available:

monitor

non-latching supervisory

non-latching drill

non-latching process monitor

process monitor

hazard

tornado

medical alert

The auto-silence timer is fixed at 20 minutes and cannot be changed.

Addressable ionization smoke detector sensitivity is automatically monitored using Canadian
specifications.

The Positive Alarm Sequence and Pre-Signal option are not available for Canadian
applications.

Waterflow Silenceable

Pressing 2 while viewing System Setup Screen #3 will allow the programmer to configure the
system for silenceable on nonsilenceable waterflow circuits. Each press of the 2 key will toggle the
display between Waterflow Sil. No and Waterflow Sil. Yes. When Waterflow Sil. No is selected, all
output devices associated with a waterflow type input device, will be nonsilenceable. When
Waterflow Sil. Yes is selected, all output devices associated with a waterflow type input device, will
be silenceable.

MNS Override

Pressing 3 while viewing System Setup Screen #3 will allow the programmer to configure the
system for use with the Mass Notification System (ECC-50/100 panel). Each press of the 3 key
will toggle the display between MNS Override No and MNS Override Yes. When MNS Override
No
is selected, the ECC-50/100 panel does not have permission to override the FACP. When MNS
Override Yes
is selected, the ECC-50/100 panel will override the FACP, taking control of its NACs
and control modules during a mass notification event. Refer to the ECC-50/100 Manual for more
information. When the Canadian Option is set to On, the MNS Override feature will become
unavailable.

Lite-Connect

Pressing 1 while viewing System Setup Screen #4 will allow the programmer to configure the
system for the Lite-Connect circuit.

Pressing 1 while viewing the Node Mode Setup Screen will allow the programmer to enable the
Lite-Connect circuit. Select Enabled Yes if an ANN-LC has been installed and wired to the
secondary ANN-BUS. Each press of the 1 key will toggle the display between Enabled No and
Enabled Yes.

SYSTEM SETUP

1=LITE-CONNECT

System Setup Screen #4

NODE MODE SETUP

1=ENABLED YES

2=ADDRESS ##

Node Mode Setup Screen