Nac (notification appliance circuit) – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 96

Advertising
background image

96

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Master Programming Level

A flashing cursor will appear in the lower left corner of the display. Type the two digit AC loss
reporting delay in hours (00 to 23 hour delay). When the second digit is entered, the display will
return to AC Loss Delay Screen #1.

NAC (Notification Appliance Circuit)

The options for the NACs on the control panel main circuit board can be configure by pressing 2
while viewing System Setup Screen #2. The following screens will be displayed:

The Notification Appliance Circuits can be configured independently by pressing 1 for NAC 1, 2
for NAC 2, 3 for NAC 3, or 4 for NAC 4.

The following screens will be displayed for each selection:

Enabled

Pressing 1 while viewing NAC Screen #1 will cause the display to change to Enabled No. This will
prevent the selected main circuit board NAC from activating its devices. Each press of the 1 key
will cause the display to toggle between Enabled Yes and Enabled No.

Type

The main circuit board NAC type can be programmed by pressing 2 while viewing NAC Screen #1.
The following screen will be displayed. Press the down arrow key to view additional screens:

Select the NAC device type by pressing the number corresponding to the type in the appropriate
screen. When the selection is made, the display will return to NAC Screen #1.

NOTE:

Upon the loss of AC power at the control panel, relays programmed for ‘AC Loss’ will

transfer immediately, regardless of the AC Loss Delay setting. If no trouble exists at the panel
other than AC Loss, the System Trouble relay will delay its activation for the duration of the AC
Loss Delay setting.

SYSTEM SETUP

1=TIMERS

2=NAC

3=RELAYS

System Setup Screen #2

NACS

1=NAC 1 3=NAC 3

2=NAC 2 4=NAC 4

NAC Selection Screen

NAC #

1=ENABLED YES

2=TYPE BELL

3=SILENCEABLE YES

NAC Screen #1

NAC #

1=ZONE

00 00 00 00 00

2=SIL INHIBITED NO

NAC Screen #2

NAC #

1=AUTO SILENCE 00

2=CODING

TEMPORAL

NAC Screen #3

NAC #

1=SYNC TYPE S

2=MNS OVERRIDE NO

NAC Screen #4

NOTE: The programming for NAC 1 will determine the operation of the remote power supply sync.

NAC #

1=ENABLED

2=TYPE

3=SILENCEABLE

NAC Screen #1

NAC TYPE

1=BELL

2=HORN

3=STROBE

Type Screen #1