8 program check, 9 history, 10 annunciators – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 148

Advertising
background image

148

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Operating Instructions

Read Status

The operator can view the programmed option for each relay by pressing the corresponding number
key.

4.23.8 Program Check

Pressing 2 while viewing Read Status Screen #3 will cause a screen similar to the following to be
displayed:

Pressing 1 while viewing the Program Check screen will display a screen which will indicate if any
input zones have not been programmed to one of the Notification Appliance Circuits. Use the up
and down arrow keys to view all NACs.

Pressing 2 while viewing the Program Check screen will display a screen which will indicate if any
output zones have not been programmed to at least one input zone. Use the up and down arrow
keys to view all zones.

Pressing 3 while viewing the Program Check screen will display a screen which will indicate if any
input zones have not been programmed to at least one output zone. Use the up and down arrow
keys to view all zones.

4.23.9 History

Pressing 3 while viewing Read Status Screen #3 will display the following screen:

The operator can view all events which have been stored in the history file, only alarms or other
events, such as troubles or supervisories, by pressing the corresponding number key.

4.23.10 Annunciators

Pressing 1 while viewing Read Status Screen #4 will display the following screens:

The Annunciator Screen indicates if Terminal mode options are enabled or disabled.

Pressing 2 for ACS Options while viewing the Annunciator Screen allows the operator to view the
ACS Options screen:

The ACS Options screen indicates if the ACS option has been enabled YES or disabled NO.

Pressing 2 for ACS Addresses while viewing the ACS Options screen will display screens with
ACS addresses 1 -31 and whether a device is installed at that address YES or not installed NO.

The ACS Options screen indicates if a UDACT is installed YES or if a UDACT is not installed NO.

PROGRAM CHECK

1=NACS NO INPUT

2=ZONES NO INPUT

3=ZONES NO OUTPUT

HISTORY

1=VIEW ALL

2=VIEW ALARMS

3=VIEW OTHER EVENTS

READ STATUS

1=ANNUNCIATORS

2=PHONE LINE

3=CENTRAL STATION

Read Status Screen #4

ANNUNCIATORS

TERM ENABLED YES

2=ACS OPTIONS

3=ANN-BUS OPTIONS

Annunciator Screen

ACS OPTIONS

ACS ENABLED NO

2=ACS ADDRESSES

UDACT ENABLED NO

ACS Options Screen

Advertising