2 zones, 3 power, Zones 4.23.3: power – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 146

Advertising
background image

146

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Operating Instructions

Read Status

Pre-Signal Yes/No (for detectors and monitor modules)

Zone Assignments (five maximum)

Chamber Value

Adjective/Noun descriptor

Silenceable Yes/No (for control modules)

MNS Override Enabled/Disabled (for control modules)

4.23.2 Zones

Pressing 2 while viewing Read Status Screen #1 will cause the following screens to be displayed:

From the preceding screens, the control panel operator can view:

Zones Installed - all software zones programmed into the system (99 maximum)

Zones Enabled - all software zones that are enabled

Zones Disabled - all software zones that have been disabled

Special Purpose - on or off programming for Special Purpose Zones 97 reserved for PAS, 98
reserved for Pre-signal and 99 reserved for Two Stage

Zone Type - the Type assigned to each installed zone (default is Alarm)

Zone Message - the Message assigned to each installed zone

4.23.3 Power

Pressing 3 while viewing Read Status Screen #1 will cause the following screens to be displayed:

The following table lists the circuit being measured, possible conditions and their respective
voltage ranges:

READ STATUS

1=SYSTEM POINT

2=ZONES

3=POWER

Read Status Screen #1

ZONES

1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zones Screen #1

ZONES

1=SPECIAL PURPOSE

2=ZONE TYPE

3=ZONE MESSAGE

Zones Screen #2

Circuit

Condition

Voltage Range

Battery

Normal Battery (nominal)

27.05 to 28.15 VDC

Low Battery

20.0 to 20.8 VDC

No Battery

0 to 18.36 VDC

24V Resettable

Normal

21.25 to 27.50 VDC

24V Nonresettable

Normal

21.25 to 27.50 VDC

Charger

Normal

21.87 to 29.84 VDC

NAC 1 - NAC 4

Normal

-1.3 to -1.6 VDC

Open Circuit

-2.3 to -2.5 VDC

Short Circuit

0 to 1.0 VDC

POWER

BATTERY 27.21V

24 V RST 25.31

Power Screen #1

POWER

CHARGER 28.36V

NAC 1 -1.49V

NAC 2 -1.49V

Power Screen #2

POWER

NAC 3 -1.49V

NAC 4 -1.49V

Power Screen #3