MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

97

Master Programming Level

Programming

The following table contains NAC type codes and their functions:

Silenceable

Pressing 3 while viewing NAC Screen #1 will cause the display to change to Silenceable No. This
will prevent the selected main circuit board NAC from being silenced by pressing the Alarm
Silence key or by the Auto Silence feature. Each press of the 3 key will cause the display to toggle
between Silenceable Yes and Silenceable No.

Important: When a Notification Appliance Circuit with a mix of audible and visual devices is
programmed for silenceable and the Synced Strobe feature is selected, only the audible devices will
be turned off if the Silence key is pressed or if the Autosilence feature is enabled. The visual devices
(strobes, etc.) will continue to operate. If the Strobe Sil Sync feature is selected, Silence or
Autosilence will turn off both audible and visual devices.

Auto Silence

The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable
notification appliances after a programmed length of time. To enable this feature and program the
time delay before Auto Silence activation, press 1 while viewing NAC Screen #2. The following
screens will be displayed:

To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1. To
enable the Auto Silence feature, press the number corresponding to the time delay which will
elapse before Auto Silence activates. This information will be stored in memory and the display
will return to NAC Screen #2.

NAC Type Code

Special Function

Bell

None

Horn

None

Strobe

None

Synced Strobe

Synchronized to manufacturer

Strobe Sil Sync

Same as Synced Strobe but Silence turns off audible & visual devices

Future Use

None

Future Use

None

Future Use

None

Blank

None

NAC #

1=AUTO SILENCE

2=CODING

TEMPORAL

NAC Screen #2

AUTO SILENCE

1=NO

2=5 MINUTES

3=10 MINUTES

Auto Silence Screen #1

AUTO SILENCE

1=30 MINUTES

Auto Silence Screen #2

AUTO SILENCE

1=15 MINUTES

2=20 MINUTES

3=25 MINUTES

Auto Silence Screen #3

NOTE: All silenceable control modules as well as the remote power supply sync will be
controlled by the Autosilence timer for NAC 1.