MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

33

Relays

Installation

2.3.2 Battery Power

The batteries must be sealed lead acid type. Before con-
necting the batteries to the FACP, make certain that the
interconnect cable between the batteries is not connected.
Do not connect the interconnect cable until the system is
completely installed. Observe polarity when connecting
the batteries. Connect the battery cable to J9 on the main
circuit board. Refer to “Power Supply Calculations” on
page 159,
for calculation of the correct battery rating.

2.3.3 Special Application DC Power Output Connection

All Special Application DC power outputs are power-limited (refer to“UL Power-limited Wiring
Requirements” on page 36
).

2.4 Relays

The FACP provides two programmable Form-C relays and one fixed fail-safe Form-C trouble
relay, all with contacts rated for 2.0 amps @ 30 VDC (resistive) or 0.5 amps @ 30 VAC (resistive).

Note that relay connections may be power-limited or nonpower-limited, provided that 0.25” spac-
ing is maintained between conductors of power-limited and nonpower-limited circuits. Refer to
UL Power-limited wiring requirements.

-

-

+

+

Interconnect
Cable

!

WARNING: RISK OF PERSONAL INJURY
BATTERY CONTAINS SULFURIC ACID WHICH CAN CAUSE SEVERE BURNS TO THE SKIN
AND EYES AND CAN DESTROY FABRICS. IF CONTACT IS MADE WITH SULFURIC ACID,
IMMEDIATELY FLUSH THE SKIN OR EYES WITH WATER FOR 15 MINUTES AND SEEK
IMMEDIATE MEDICAL ATTENTION.

+ 24V -

NON-RST

POWER

+ 24V -

RST

POWER

3

2

1

1

2

3

1 2 3 4

+ - + -

Figure 2.6 Special Application Power Outputs - 24 VDC

Power-limited Non-resettable or Resettable Power
1.0 amperes max., 24 VDC nominal filtered, non-
resettable or resettable power can be drawn from TB1
Terminals 1(+) and 2(-)

Power-limited Resettable or Non-resettable Power
1.0 amperes max., 24 VDC nominal filtered, resettable or
non-resettable power can be drawn from TB1 Terminals
3(+) and 4(-)

9

2

u

d

c

tb

1

.w

m

f

JP4

TB1

JP4 is used to configure TB1,
Terminals 1 & 2 for:
• Resettable Power - jumper pins
2 & 3 of JP4
• Nonresettable Power - jumper
pins 1 & 2 of JP4 as shown

JP6

JP6 is used to configure TB1,
Terminals 3 & 4 for:
• Resettable Power - jumper pins 2
& 3 of JP4
• Nonresettable Power - jumper
pins 1 & 2 of JP4 as shown

Figure 2.7 Relay Terminals

Relay contacts shown with power
applied to panel and no active
troubles, alarms or supervisories

TB7

Note that the programmable relay
labeled as Relay 1 is factory default
programmed as Alarm and
programmable Relay 3 is factory default
programmed as Supervisory.
The relay labeled Relay 2 is fixed as a
Trouble relay and cannot be changed.
It is a fail-safe relay which will transfer
on any trouble or total power failure.