5 notification appliance circuits, 1 style y (class b) nac wiring, Notification appliance circuits – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 34: Style y (class b) nac wiring

Advertising
background image

34

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Installation

Notification Appliance Circuits

2.5 Notification Appliance Circuits

The control panel provides four Style Y (Class B) or four Style Z (Class A) NACs (Notification
Appliance Circuits) when using the optional ZNAC-92 Class A converter module. Each circuit is
capable of 2.5 amps of current. Total current in alarm for all external devices cannot exceed 6.0
amps (refer to “Calculating the System Current Load” on page 159). Use UL listed 24 VDC notifi-
cation appliances only. Circuits are supervised and power-limited. Refer to the Device Compatibil-
ity Document
for a listing of compatible notification appliances. The NACs, which are located on
the main circuit board, may be expanded via the FCPS Series field charger/power supplies.

The following sections describe the configuration and wiring of Style Y and Style Z Notification
Appliance Circuits on the MS-9200UDLS main circuit board.

2.5.1 Style Y (Class B) NAC Wiring

Figure 2.8 NAC Style Y (Class B) Wiring

4 Style Y (Class B) Notification Appliance Circuits, supervised and power-limited - 4.7 k

, ½ watt P/N:71252 UL listed

Polarized Bells

Polarized Bells

Polarized Horns

Polarized Horns

Polarized Strobes

Notification Appliance Circuit
polarity shown in alarm state

Dummy Load all unused circuit

TB4

9

2

0

0

n

a

c

y

.w

m

f

Polarized Strobes

circuit number

NAC 1

NAC 3

NAC 4

NAC 2

TB3