MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Operating Instructions

Read Status

Communication Format

Event Codes

4.23.13 Service Terminal

Pressing 1 while viewing Read Status Screen #5 will display the following screens:

The Ring Count is displayed in the Service Terminal Screen.

4.23.14 Printer/PC

Pressing 2 while viewing Read Status Screen #5 will display the following screen:

The display will inform the operator as to whether the control panel is configured for a printer or a
PC. In the example above, PR4800 indicates that the panel is configured for a printer with a baud
rate of 4,800.

4.23.15 Print

To print program data or control panel status, press 3 while viewing Read Status Screen #5. The
following screens will be displayed:

Pressing 1 while viewing Print Screen #1 allows the user to print the History file which will detail
all of the system activities since the file was last cleared from memory.

Pressing 2 while viewing Print Screen #1 allows the user to print the Walktest log which will detail
all of the system activations during walktest since the log was last cleared. Refer to “Walktest” on
page 103 for
additional information on the display.

Pressing 3 while viewing Print Screen #1 allows the user to print the detector data for each
addressable smoke detector connected to the system. A printout, similar to the following example,
will be generated if an optional printer is connected to the FACP.

READ STATUS

1=SERVICE TERMINAL

2=PRINTER/PC

3=PRINT

Read Status Screen #5

SERVICE TERMINAL

RING COUNT

Service Terminal Screen

PRINTER PC

PRINTER PC PR4800

Printer/PC Screen

READ STATUS

1=FUTURE USE

2=PRINTER/PC

3=PRINT

Read Status Screen #5

PRINT

1=HISTORY

2=WALKTEST LOG

3=DETECTOR DATA

PRINT

1=EXIT PRINTING

Print Screen #2

Print Screen #1