4 digital alarm communicator/transmitter, 5 components – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 18

Advertising
background image

18

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Product Description

Digital Alarm Communicator/Transmitter

Key Panel

Mounted on the main circuit board, the key panel includes a window for the LCD display and LED
indicators as listed above. The key panel, which is visible with the cabinet door closed, has 25
keys, including a 16 key alpha-numeric pad similar to a telephone keypad.

Function keys:

Acknowledge/Step

Alarm Silence

Drill

Reset (lamp test)

Service/program keys:

Keys labeled 1 to 9

* key

# key

0 (recall) key

1st Event key

Clear key

Escape key

Mode key

Four cursor keys (up, down, left and right)

Enter key

Local Piezo Sounder

A piezo sounder provides separate and distinct pulse rates for alarm, trouble and supervisory condi-
tions.

1.4 Digital Alarm Communicator/Transmitter

Two modular phone jacks allow easy connection to telephone lines. Modular jacks are labeled PH1
for Primary Phone Line and PH2 for Secondary Phone Line. Two telephone line active red LEDs
are provided as well as a green Kissoff LED. The integral digital communicator provides the fol-
lowing functions:

Line Seizure: takes control of the phone lines disconnecting any premises phones

Off/On Hook: performs on and off-hook status to the phone lines

Listen for dial tone: 440 Hz tone typical in most networks

Dialing the Central Station(s) number: default is Touch-Tone

®

, programmable to rotary

For tone burst or touchtone type formats: discern proper Ack and Kissoff tone(s). The
frequency and time duration of the tone(s) varies with the transmission format. The control
panel will adjust accordingly.

Communicate in the following formats:

Ademco Contact ID

SIA DCS 8

SIA DCS 20

1.5 Components

Main Circuit Board

The main circuit board contains the system’s CPU, power supply, other primary components and
wiring interface connectors. The 4XTMF option module plugs in and is mounted to the main cir-
cuit board.