Page 62

Advertising
background image

62

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Installation

Automatic Audio Panel Control

Connect the ECC-50/100 panel’s FACP Data Bus at TB13 to TB9 on the MS-9200UDLS FACP.

The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair of commu-
nication wires connected between the A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals
2 & 3 of the ACC-ZPMK module on the audio panel.

+ -

B+ A+ B- A- A B

ACS

SHIELD

SLC

SLC

SLC

SLC

OUT+ IN+ OUT- IN-

TB8

TB9

TB10

Figure 2.35 FACP Connection to ECC-50/100 Series Audio Panel