11 clear program, 12 program check, Clear program 3.6.12: program check – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 126

Advertising
background image

126

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Master Programming Level

The following screen will appear when any change option is selected:

A flashing cursor will appear in the center of the display. Enter a new five digit password (such as
10101 for the Master Level). After the fifth digit is entered, the following screen will be displayed:

Re-enter the new password to accept the change. The display will return to the initial Password
Change Screen.

3.6.11 Clear Program

Pressing 2 while viewing Programming Screen #4, will select the Clear Program option. This will
cause the LCD to display the following screen:

Pressing 1, for Whole System while viewing the Clear Program Screen #1, will clear all general
system programming options and all programmed addressable devices from the nonvolatile
memory of the FACP. This function is useful when the control panel is first installed, prior to
autoprogramming. Note that it is necessary to autoprogram after using the Clear Whole System
function.

Pressing 2, for ALL POINTS while viewing the Clear Program Screen #1, will clear all
programming related to the SLC loop and connected addressable devices.

Before executing any of the Clear commands listed above, the control panel will provide a warning
to the user by prompting with the following display:

Pressing 1 will cause the control panel to carry out the selected clear option. Pressing 2 will
prevent programming from being cleared.

3.6.12 Program Check

The Program Check feature allows the programmer to view the zones which have been
programmed to the Notification Appliance Circuits on the control panel but have not been
programmed to Initiating Devices as well as other circuits with no input or output correlations.
Pressing 3 while viewing Programming Screen #4 will cause the following screen to be displayed:

ENTER NEW FIVE DIGIT

PASSWORD

Enter Password Screen

VERIFY NEW PASSWORD

Password Change Screen

PROGRAMMING

1=PASSWORD CHANGE

2=CLEAR PROGRAM

3=PROGRAM CHECK

Programming Screen #4

CLEAR PROGRAM

1=WHOLE SYSTEM

2=ALL POINTS

Clear Program Screen #1

WARNING!

SYSTEM CHANGE

PROCEED?

1=YES 2=NO

PROGRAMMING

1=PASSWORD CHANGE

2=CLEAR PROGRAM

3=PROGRAM CHECK

Programming Screen #4

PROGRAM CHECK

1=NACS NO INPUT

2=ZONES NO INPUT

3=ZONES NO OUTPUT

Advertising