Optional Module Installation

Installation

The following table shows the ANN-80 connections to the MS-9200UDLS.

Programming

Following installation and wiring of the ANN-80 LCD annunciator to the FACP, the annunciator
must be added to the system via FACP programming. Refer to the programming section titled
“ANN-BUS Options” on page 107 in this manual for detailed programming information. Select
the LCD option for programming.

Trouble Response

If the ANN-80 is installed but the ANN-BUS is not enabled at the FACP, the ANN-80 will indicate
a trouble condition by NOT turning on its AC Power indicator. The LCD will also display Key Bus
Trouble
and the piezo will sound approximately once every 10 seconds. Note that the FACP will
provide no indication of an ANN-80 trouble.

To clear the ANN-80 trouble condition, enable the ANN-BUS and program the address correspond-
ing to the address set on the ANN-80 at the FACP.

ANN-S/PG Serial/Parallel Interface Module

Installation

1.

Ensure that all power (AC and DC) has been removed from the FACP.

2.

Connect the ANN-S/PG to the FACP as illustrated in Figure 2.22

3.

Using the DIP switches on the back of the ANN-S/PG module, assign an ID number (address)
to the module

4.

Select the address and configuration options for the ANN-S/PG module as described in the
Programming section of this manual (refer to “ANN-BUS Options” on page 107)
Note that the Auto-configure feature allows the programmer to quickly bring all installed
ANN-BUS modules online (refer to “Auto-Configure” on page 116)

MS-9200UDLS

ANN-80 (TB1)

Terminal GND (-) on TB1

Terminal 1 (-)

Terminal PWR (+)TB1

Terminal 2 (+)

Terminal Data (A) on TB9

Terminal 3 (A)

Terminal Data (B) on TB9

Terminal 4 (B)

(-)

(+)

A
B

B+ A+ B- A- A B

ANN
ACS

SHIELD

SLC

SLC

SLC

SLC

TB9

TB10

A B

+ -

+ 24V -

NON-RST

POWER

+ 24V -

RST

POWER

TB1

JP7

1
2

3

+ -

REMOTE PWR
SUPPLY SYNC

+ -

TB2

Figure 2.22 ANN-S/PG Connection to FACP

ANN-S/PG Module

Cable Connectors for
connection to printer

Parallel

Serial

ANN-BUS and power wiring are
supervised and power-limited

24 VDC
nonresettable

Primary ANN-BUS

9