NAC Wiring

Wire Requirements

E.1 NAC Wiring

The following table lists NAC wiring requirements for the FACP.

Notes:

1.

Calculations are based on Direct-Current Resistance data for uncoated copper wire, per
National Electrical Code (2005 Edition) Table 8, Conductor Properties.

NAC Load

(Amps)

Max.

allowable

total loop

resistance

(ohms)

CLASS-B

Max. allowable wire pair length

(feet)

CLASS-A

Max. allowable wire pair length

(feet)

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

AWG 12

solid

AWG 14

solid

AWG 16

solid

AWG 18

solid

0.25

12.72

3295

2072

1301

819

1648

1036

650

409

0.5

6.36

1648

1036

650

409

824

518

325

205

0.75

4.24

1098

691

434

273

549

345

217

136

1

3.18

824

518

325

205

412

259

163

102

1.25

2.54

659

414

260

164

330

207

130

82

1.5

2.12

549

345

217

136

275

173

108

68

1.75

1.82

471

296

186

117

235

148

93

58

2

1.59

412

259

163

102

206

129

81

511

2.25

1.41

366

230

145

91

183

115

72

45

2.5

1.27

330

207

130

82

165

104

65

41

Table E.2 NAC Wiring Requirements for FACP