Appendix I: Canadian Application

The MS-9200UDLSC is supplied with the DP-9692 Dress Panel.

When installing and programming the FACP, the Canadian Option must be set to ON prior to
any other panel programming (refer to “Canadian Option” on page 100 of the Programming
Section of this manual).

ACS Series annunciators are not compatible for Canadian applications.

At least one ANN-LED must be installed adjacent to the FACP as it is part of the primary
operator interface. Wiring to the ANN-LED must be in metal conduit and must be connected
to the FACP’s Primary ANN-BUS.

If remote indicators are desired, they must be connected to the Secondary ANN-BUS circuit
and the other special application power output.

The installer must write in the Date of Final Assembly on the Master Marking and Warranty
Label located on the FACP backbox door.

To comply with CAN/ULC-S559-04, the 4XTMF option must be utilized along with the
configuration shown in Figure I.3.

Positive Alarm Sequence (PAS), the Pre-Signal option, and the Silence Inhibit Timer are not
available for Canadian applications.

FIRE SYSTEM
ACTIVE

SYSTEM

CONTROL

ALL

CALL

1

2

3

4

5

6

7

8

9

10

11

12

13

18

19

20

21

22

23

24

16

17

14

15

LIT

FI

®

AL

by Honeywell

Figure I.1 FACP Minimum Configuration - Single ANN-LED

FACP

ANN-LED

ANN-LED

ANN-80C

ANN-I/O

ANN-S/PG

ANN-RLY

Optional Secondary ANN-BUS (data on

connector TB8, power on TB1 Terminals

3&4 with JP6 pins 1&2 jumpered)

Primary ANN-BUS

(data on connector

TB9, power on TB1

Terminals 1&2)

in metal conduit

(adjacent to FACP)

9

2

0

0

u

ls

c

-a

n

n

le

d

.w

m

f

optional

ECC-50/100

audio system

Advertising