3 program check, Program check – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 129

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

129

Maintenance Programming Level

Programming

will be displayed on the screen. To view all of the selected events, press the up or down arrow keys
to scroll through the list of events. If no events have occurred, the display will read NO EVENTS
IN HISTORY.

Pressing 2 while viewing the History Screen will cause the following screen to be displayed:

Pressing 1 while viewing the Erase History Screen will cause the message ERASING HISTORY,
PLEASE WAIT
to be displayed. The display will then return to the History Screen. Pressing 2 will
cause the display to return to the History Screen without erasing the History file.

3.7.3 Program Check

Pressing 3 while viewing Maintenance Screen #1 will cause the following screen to be displayed:

The Program Check feature allows the programmer to view the zones which have been
programmed to the Notification Appliance Circuits on the control panel but have not been
programmed to Initiating Devices as well as other circuits with no input or output correlations.
Pressing 1 while viewing Program Check screen will cause a screen similar to the following to be
displayed.

The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for both NAC 1, NAC 2, NAC 3 and NAC 4.

Pressing 2 while viewing the Program Check screen will display a screen similar to the following:

The Zone No Input screen allows the programmer to view the zones which have not been
programmed to at least one input device (not including general alarm Zone 00). The example in the
preceding screen indicates that Zones 05, 07, 09, 10 and 11 have been programmed to an
addressable module (control module in this example) with an address of 001 on loop 1 but have not
been programmed to any input devices. Use the up and down arrow keys to view all the zones
without input assignments.

Pressing 3 while viewing Program Check screen will cause a screen similar to the following to be
displayed:

ERASE HISTORY

PROCEED ?

1=YES 2=NO

Erase History Screen

PROGRAMMING

1=POINT PROGRAM

2=HISTORY

3=PROGRAM CHECK

Maintenance Screen #1

PROGRAM CHECK

1=NACS NO INPUT

2=ZONES NO INPUT

3=ZONES NO OUTPUT

Program Check Screen

NACS NO INPUT

NAC 1

25 31 44 55 67

ZONES NO INPUT

05 07 09 10 11 1M001

ZONES NO OUTPUT

05 07 09 10 11 1D001

Advertising