Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 48

Advertising
background image

48

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Installation

Optional Module Installation

Wiring ANN-80 to FACP

The following steps can be used as a guide to wire the annunciator. Make certain all power has
been removed from the FACP prior to annunciator installation.

1.

Route wires from hole in backplate, through wiring channel and then to ANN-80 terminal
block TB1

2.

Remove appropriate amount of wire insulation

3.

Connect the wiring from the FACP ANN-BUS to annunciator TB1 terminals 3 (A) & 4 (B).
Make certain to connect A to A and B to B

4.

If appropriate, connect the wiring going to the next device on the ANN-BUS to TB1 terminals
3 & 4. Make certain to connect A to A and B to B

5.

Connect the wiring from the 24 VDC power source to annunciator TB1 terminals 1 (-) & 2 (+).
Make certain to observe proper polarity

6.

If appropriate, connect the power wiring going to the next device to terminals
1 (-) & 2 (+). Make certain to observe proper polarity

7.

After all connections are made, remove extra wire from inside of annunciator by dressing it
neatly through wire channel, with any excess wire pushed back through hole into electrical box

wiring channel

wires

TB1

a

n

n

-8

0

b

o

x

in

s

id

e

.w

m

f

B+ A+ B- A- A B

ANN
ACS

SHIELD

SLC

SLC

SLC

SLC

TB9

TB10

TB1

B A (+) (-)

4 3 2 1

A B

+ -

+ 24V -

NON-RST

POWER

+ 24V -

RST

POWER

TB1

JP7

1

2

3

+ -

REMOTE PWR
SUPPLY SYNC

+ -

TB2

Figure 2.21 ANN-80 Wiring to FACP

ANN-80

ANN-BUS and power wiring are
supervised and power-limited

24 VDC
nonresettable

ANN-BUS

9

2

u

d

ls

c

to

a

n

n

8

0

.w

m

f

Primary ANN-BUS

MS-9200UDLS

Advertising