Zone assignment, Noun/adjective, Zone assignment noun/adjective – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 84

Advertising
background image

84

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Master Programming Level

Zone Assignment

A maximum of five zones can be programmed to each addressable control module. Pressing 2
while viewing Edit Control Screen #3 displays the following screen:

Note that Z** represents the Zone Number(s) corresponding to this device. The factory default for
an unprogrammed device is Z00 for general alarm zone. A flashing cursor will appear on the first 0
to the left. Enter the two digit number corresponding to the zone that is to be assigned to this
device. The cursor moves to the next Z** designation. Continue entering zone assignments or the
remaining zones can be left blank or programmed as general alarm zones Z00. When all desired
changes have been made, press the Enter key to store the zone assignments. The display will return
to the Edit Control Screen #3.

Noun/Adjective

The Noun/Adjective selection allows the programmer to enter specific descriptors about the control
module currently being programmed. Pressing 1 while viewing Edit Control Screen #4 will cause
the following screen to be displayed:

ZONE ASSIGNMENT

Z00 Z Z Z Z

Zone Assignment Screen

EDIT CONTROL

1=NOUN/ADJECTIVE

2=DESCRIPTION

Edit Control Screen #4

1=STANDARD ADJECTIVE

2=STANDARD NOUN

3=CUSTOM ADJECTIVE

4=CUSTOM NOUN

Noun/Adjective Screen

Advertising