MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

89

Master Programming Level

Programming

Zone Type

Zone Types must be programmed only if a DACT, programmed for zone reporting, is installed on
the control panel. Pressing 1 for Zone Types, while viewing Zone Setup Screen #3, will display a
screen similar to the following:

This display will show the system zones (default and user programmed) and their associated types.
Note that an up and/or down arrow will appear in the upper right corner of the display, indicating
that additional screens of zone information exists. Press the up or down arrow keys to view zones
Z00 through Z99.

Zone types can be changed by pressing the keypad number key corresponding to the zone in each
Zones Installed Screen. Available zone types will be displayed in the resultant screens. For
example, to change the zone type for zone Z02 in the screen illustrated above, press 3. The
following screens will be displayed:

To change the zone type for Z02 to Pull Station, scroll the display until Zone Type Program Screen
#2 is displayed. Press 2 to program zone Z02 as a Pull Station zone. The display will return to the
Zones Installed Screen showing zone Z02 and the Pull Station program type. Repeat the procedure
for each zone to be changed.

IMPORTANT! In Zone Type Program Screen #1, selecting WATERFLOW will assign a Waterflow
silenceable zone type to the selected zone. Any signaling devices programmed to the same zone can
be silenced by pressing the Alarm Silence key or by using the auto-silence feature.

To program a waterflow circuit as nonsilenceable, refer to “System Setup” on page 91.

Zones Available

Pressing 2 while viewing Zone Setup Screen #3 will display the following screen:

The display will show all of the zones that are still available for programming. Note that an up
and/or down arrow may appear in the upper right corner of the display, indicating that additional
screens of zone information exists. Press the up or down arrow key to view additional screens.

ZONE SETUP

1=ZONE TYPES

2=ZONES AVAILABLE

3=ZONE MESSAGE

Zone Setup Screen #3

ZONE TYPE PROG

1=Z00 MONITOR

2=Z01 MONITOR

3=Z02 MONITOR

Zones Installed Screen

ZONE TYPE PROG

1=MONITOR

2=SMOKE PHOTO

3=WATERFLOW

Zone Type Program Screen #1

ZONE TYPE PROG

1=MEDICAL

2=HAZARD

3=TAMPER

Zone Type Program Screen #2

ZONE TYPE PROG

1=SUPERVISORY

2=PROC. MON

3=SMOKE ION

Zone Type Program Screen #4

ZONE TYPE PROG

1=HEAT

2=PULL STATION

3=DUCT

Zone Type Program Screen #3

NOTE: Zone Types are only relevant for Central Station reporting. Changing a zone type will
only change how it is reported to the Central Station.

ZONE SETUP

1=ZONE TYPES

2=ZONES AVAILABLE

3=ZONE MESSAGE

Zone Setup Screen #3

ZONES AVAILABLE

01 02 03 04 05 06 07

08 09 10 11 12 13 14

15 16 17 18 19 20 21