3 zone setup, Enable, Disable – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 87: Zone 97, 98 and 99, Zone setup, Enable disable zone 97, 98 and 99

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

87

Master Programming Level

Programming

3.6.3 Zone Setup

Pressing 3 while viewing Programming Screen #2 will access the Zone Setup screens as illustrated
below:

Enable

Pressing 1 for Enable, while viewing Zone Setup Screen #1, will display the following screen:

This screens allows the programmer to enable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be enabled and the cursor returns to the original position next to the Z.
Another zone can then be enabled.

Disable

Pressing 2 for Disable, while viewing Zone Setup Screen #1, displays the following:

This screen allows the programmer to disable zones, one at a time. A flashing cursor appears next
to the Z, prompting the programmer to enter a two digit zone number (01 - 99). When the second
digit is entered, the zone will be disabled and the cursor will return to the original position next to
the Z. Another zone can then be disabled.

Zone 97, 98 and 99

Pressing 3 for Zone 97, 98 and 99, while viewing Zone Setup Screen #1, will display the following
screen:

Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose
applications. In the above illustration, the three zones are shown Off, which means they can be
programmed to function in the same manner as all other zones, by assigning them to input and
output devices in the Programming Zone Assignment Screen.

Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the
display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 97 to activate. By
assigning Zone 97 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control

PROGRAMMING

1=AUTOPROGRAM

2=POINT PROGRAM

3=ZONE SETUP

Programming Screen #2

ZONE SETUP

1=ENABLE

2=DISABLE

3=ZONE 97 98 99

Zone Setup Screen #1

ZONE SETUP

1=ZONES INSTALLED

2=ZONES ENABLED

3=ZONES DISABLED

Zone Setup Screen #2

ZONE SETUP

1=ZONE TYPES

2=ZONES AVAILABLE

3=ZONE MESSAGE

Zone Setup Screen #3

ZONE SETUP

1=ENABLE

2=DISABLE

3=ZONE 97 98 99

Zone Setup Screen #1

ZONE TO ENABLE

Z

Enable Screen

ZONE SETUP

1=ENABLE

2=DISABLE

3=ZONE 97 98 99

Zone Setup Screen #1

ZONE TO DISABLE

Z

Disable Screen

SPEC PURPOSE ZONE

1=PAS 97 OFF

2=PRESIGNAL 98 OFF

3=TWO STAGE 99 OFF

Zone 97, 98 and 99 Screen

Advertising