MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Installation

Optional Module Installation

Wiring Configuration

Figure 2.18 illustrates the wiring between the FACP’s Primary ANN-BUS and ANN-BUS devices.

Figure 2.19 illustrates the wiring between the FACP’s Secondary ANN-BUS and ANN-BUS
devices.

Powering Both ANN-BUS Circuits Simultaneously

When simultaneously using the Primary and Secondary ANN-BUS circuits on the FACP, power
can be shared from the Nonresettable Power output on TB1. Alternately, one ANN-BUS can be
powered by the Resettable Power output (TB1 Terminals 3 and 4) once it is reconfigured as Nonre-
settable Power using JP6. This provides the benefit of independently acting power-limiting for the
two ANN-BUS circuits (required for Canadian applications).

B+ A+ B- A- A B

ANN
ACS

SHIELD

SLC

SLC

SLC

SLC

TB9

TB10

TB1

B A (+) (-)

4 3 2 1

A B

+ -

+ 24V -

NON-RST

POWER

+ 24V -

RST

POWER

TB1

JP7

1

2

3

+ -

REMOTE PWR
SUPPLY SYNC

+ -

TB2

Figure 2.18 Primary ANN-BUS wiring to ANN-BUS Device

ANN-BUS Device

MS-9200UDLS

ANN-BUS and power wiring are
supervised and power-limited

24 VDC
nonresettable

Primary ANN-BUS

9

2

u

d

ls

c

to

a

n

n

8

0

.w

m

f

+ 24V -

NON-RST

POWER

+ 24V -

RST

POWER

B+ A+ B- A- A B

ANN
ACS

SHIELD

SLC

SLC

SLC

SLC

TB1

TB8

TB9

TB10

JP7

1

2

3

TB1

B A (+) (-)

4 3 2 1

A B

+ -

+ -

REMOTE PWR
SUPPLY SYNC

+ -

TB2

Xmt Rcv Dtr Gnd
A B
In+ In- Out+ Out-

Figure 2.19 Secondary ANN-BUS wiring to ANN-BUS Device

ANN-BUS Device

MS-9200UDLS

ANN-BUS and power wiring are
supervised and power-limited

24 VDC
nonresettable

Secondary ANN-BUS

9

2

u

d

ls

c

2

to

a

n

n

8

0

.w

m

f