Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 174

Advertising
background image

174

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

NFPA Standard-Specific Requirements

Central Station/Remote Station Transmitter: Connection to FACP Dry Contacts

C.1 Central Station/Remote Station Transmitter: Connection

to FACP Dry Contacts

The dry contacts of the FACP programmable relays can be used to trip a UL-864 Listed Central
Station/Remote Station Transmitter. The FACP contacts must be supervised by the Central
Station/Remote Station Transmitter module using End-of-Line Resistors (ELRs) with a value
determined by the Transmitter manufacturer. Power is also provided by the Central Station/Remote
Station Transmitter manufacturer. Refer to the Central Station/Remote Station Transmitter
manufacturer’s manual for details.

O

U

T

+

RELAY 3

RELAY 1

RELAY 2

NO NC C

NO NC C

NC NO C

TB5

TB6

TB8

TB9

TB10

JP2

TB7

Xmt Rcv Dtr Gnd
A B
In+ In- Out+ Out-

+ -
A B

B+ A+ B- A- A B
Slc Slc Slc Slc Shield

Figure C.4 FACP Dry Contacts Connection to Central Station/Remote Station Transmitter

Typical Central Station/Remote Station Transmitter Module

Typical Input Zone Triggers

FACP Main Circuit Board

Al

arm

Tr

ouble*

Sup

e

rv

is

or

y

*Note: The Trouble Relay is a fail-safe
relay. With power applied to the FACP
and no troubles in the panel, the wiring
should be connected to the NO and C
contacts as indicated in the illustration.

m

s

9

2

0

0

u

d

ls

c

d

ry

x

m

it

.w

m

f

Advertising