MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Installation

Optional Module Installation

Switch 5 must be set to OFF for ANN-BUS devices to be recognized.

ANN-80 Remote Fire Annunciator

Specifications

Operating Voltage Range: 18 VDC to 28 VDC

Current Consumption @ 24 VDC nominal (filtered and nonresettable):

Normal/Standby (no activity): 37.0 mA

Trouble: 39.0 mA

Alarm: 40.0 mA

AC Fail ( not backlit): 15.0 mA

For use indoors in a dry location

Installation

Ensure that all power (AC and DC) has been removed from the FACP before installing the annunci-
ator.

Opening/Closing Annunciator

The following procedure details the steps used to open the annunciator in order to access the termi-
nal block and DIP switches (refer to figure below):

1.

Turn the key switch to the ON (Unlocked) position by turning the key counter-clockwise.

2.

Push in the snap latch located on the right side of the unit while pulling the cover open.

3.

To close the cover, make certain the key switch is in the ON (Unlocked) position. Swing the
cover closed, snapping it shut.

Address

Switch 5

Switch 4

Switch 3

Switch 2

Switch 1

not valid

OFF

OFF

OFF

OFF

OFF

01

OFF

OFF

OFF

OFF

ON

02

OFF

OFF

OFF

ON

OFF

03

OFF

OFF

OFF

ON

ON

04

OFF

OFF

ON

OFF

OFF

05

OFF

OFF

ON

OFF

ON

06

OFF

OFF

ON

ON

OFF

07

OFF

OFF

ON

ON

ON

08

OFF

ON

OFF

OFF

OFF