Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 69

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

69

Master Programming Level

Programming

If no detectors have been installed on the loop, the following will be displayed:

If the selected address has been added to programming, device summary screens will be displayed.
These screens allow the programmer to view all device settings at a single glance. Pressing the left
or right arrow keys will allow the programmer to rapidly view the devices at the previous or next
address (if installed).

If a detector (such as a photoelectric detector) with the selected address is not physically installed
on the SLC or has a communication fault but the address is programmed in the system, the
following screen will be displayed:

If the selected address has been added to programming and a detector (such as a photoelectric
detector) with the selected address is physically installed on the SLC and is communicating with
the control panel, the following will be displayed:

To change the programming for the displayed detector, press the keyboard ‘down’ arrow key to
view the Edit Detector screens.

In the preceding example:

Normal - indicates that the detector with the selected address is physically installed on the
SLC and communicating with the control panel (enabled)

<ADJ><NOUN> - represents the adjective and noun, which have been programmed,
describing the location of the displayed device

ZNNN - represents the first of five possible software zones that the detector is assigned to
(NNN = the three digit zone number from 000 - 099)

V or * - indicates whether or not alarm verification is enabled (V = alarm verification
enabled and * = alarm verification disabled)

1D017 - represents the Loop, Device type and Device address (1 = SLC Loop, D=Detector
and 017 = Detector Address 017)

The following examples show the editing of a photoelectric smoke detector with address 017,
located on the SLC loop:

NO DETECTOR

INSTALLED

Edit Detector Screen #1

TROUBL SMOKE(PHOTO)

<ADJ><NOUN>

ZNNN

 1D017

Edit Detector Screen #1

NORMAL SMOKE (PHOTO)

<ADJ><NOUN>

ZNNN

V 1D017

Edit Detector Screen #1

EDIT DETECTOR 1D017

1=ENABLED YES

2=TYPE SMOKE(PHOTO)

3=VERIFICATION OFF

Edit Detector Screen #2

EDIT DETECTOR 1D017

1=WALKTEST NO

2=PAS NO

3=PRE-SIGNAL NO

Edit Detector Screen #3

EDIT DETECTOR 1D017

1=ZONE ASSIGNMENT

00 

Edit Detector Screen #4

Edit Detector Screen #5

EDIT DETECTOR 1D017

1=NOUN/ADJECTIVE

2=DESCRIPTION


Advertising