Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 106

Advertising
background image

106

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Master Programming Level

Annunciator addressing is specific to the MS-9200UDLS control panel. The following table
describes the annunciator addresses and the corresponding addressable devices that will be annun-
ciated at each annunciator address.

The MS-9200UDLS must be programmed for the annunciators installed on the system. Refer to
“Annunciators” on page 105 for information on annunciator programming. Make certain to
program the annunciator addresses that have been physically installed on the system.

ACS Annunciator Address

Annunciator Displays the Following Points

1

8 General System Status Points & Zones 1 - 56

2

Zones 57 - 99 & 4 NACs

3

SLC Loop, Module Addresses 1 - 64

4

not used

5

SLC Loop, Module Addresses 65 - 99

6

not used

7

not used

8

SLC Loop, Detector Addresses 1 - 64

9

not used

10

SLC Loop, Detector Addresses 65 - 99

11

not used

12

not used

13

not used

14

not used

15

not used

16

not used

17

not used

18

not used

19

not used

20

8 General System Status Points & Zones 1 - 56

21

Zones 57 - 99 & 4 NACs

22

SLC Loop, Module Addresses 1 - 64

23

not used

24

SLC Loop, Module Addresses 65 - 99

25

not used

26

not used

27

SLC Loop, Detector Addresses 1 - 64

28

not used

29

SLC Loop, Detector Addresses 65 - 99

30

not used

31

not used

32

not used

NOTE: The 8 General System Status Points include the following:

General Alarm
General Trouble
General Supervisory
Alarm Silenced
System Off Normal
AC Loss
Battery Fault
NAC Fault