Installation

UL Power-limited Wiring Requirements

2.7 UL Power-limited Wiring Requirements

Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All
power-limited circuit wiring must remain at least 0.25” (6.35 mm) away from any nonpower-lim-
ited circuit wiring and nonpower-limited circuit wiring must enter and exit the cabinet through dif-
ferent knockouts and/or conduits. When connecting the ground cables, be sure that the AC mains
ground is the first one installed, closest to the backbox. A typical wiring diagram for the MS-
9200UDLS is shown below.

Figure 2.11 Typical UL Power-limited Wiring Requirements