178

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Wire Requirements

CIRCUIT CONNECTIONS

WIRE REQUIREMENTS

Circuit Type

Circuit Function

Wire Type and Limitations

Recommended
Max. Distance
Feet (meters)

Wire Gauge and Compatible Brands

SLC loop
(power-limited)

Connects to
Addressable
Devices

CLIP MODE

Twisted, shielded pair
40 ohms maximum per
length of Style 6 and 7
loops. 40 ohms per branch
maximum for Style 4 loops

10,000 (3,000 m)
8,000 (2,400 m)
4,875 (1,450 m)
3,225 (980 m)

12 AWG (3.25 mm

2

): Genesis 4410,

Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm

2

):Genesis 4408 & 4608

Signal 98430, Belden 9581, WPW995
16 AWG (1.30 mm

2

): Genesis 4406 & 4606

Signal 98630, Belden 9575, WPW991
Direct Burial Cable Isotec NP713110VNQ-S
18 AWG (0.75 mm

2

): Genesis 4402 & 4602

Signal 98300, Belden 9574, WPW975
Direct Burial Cable Isotec NP714110VNQ-S

LITESPEED
MODE

Twisted, unshielded pair
40 ohms maximum per
length of Style 6 and 7
loops. 40 ohms per branch
maximum for Style 4 loops

10,000 (3,000 m)
8,000 (2,400 m)
4,875 (1,450 m)
3,225 (980 m)

12 AWG (3.25 mm

2

): Belden 5020UL &

6020UL, Genesis WG-4315 & WG-4515
14 AWG (2.00 mm

2

):Belden 5120UL &

6120UL, Genesis WG-4313 & WG-4513
16 AWG (1.30 mm

2

): Belden 5220UL &

6220UL, Genesis WG-4311 & WG-4511
18 AWG (0.75 mm

2

): Belden 5320UL &

6320UL, Genesis WG-4306 & WG-4506

Untwisted, unshielded pair

1

3,000 (900 m)

12-18 AWG (3.25 - 0.75 mm

2

) using listed wire

ACS-BUS
(EIA-485)
(power-limited)

Connects to
annunciator
modules/
ECC-50/100

Twisted pair with a
characteristic impedance of
120 ohms

6,000 (1,800 m)

12 AWG (0.75 mm

2

)

ANN-BUS
(EIA-485)
(power-limited)

Connects to
annunciator
modules/
ECC-50/100

Twisted pair

6,000 (1,800 m)

Refer to “ANN-BUS Wiring” on page 42 for
information on device wiring

EIA-232
(power-limited)

connects to remote
PC computer

Twisted, shielded pair

50 (15 m)

18 AWG (0.75 mm

2

) minimum

MMF-300 and
MMF-301
(power-limited)

Initiating Device
Circuit: Contact
Closure

Maximum loop wire
resistance is 1500 ohms

2,500 (760 m)

12-18 AWG (3.25 - 0.75 mm

2

)

MMF-302
(power-limited)

Initiating Device
Circuit: Two-wire
Modules

No more than a 2.4 volt
drop allowed at end of
circuit. Maximum loop wire
resistance is 25 ohms

2,500 (760 m)

12-18 AWG (3.25 - 0.75 mm

2

)

CMF-300
(power-limited)

Notification
Appliance Circuit

In alarm, no more than a 1.2
volt drop allowed at end of
circuit

Distance limitation
set by 1.2 volt
maximum line drop

12-18 AWG (3.25 - 0.75 mm

2

)

Remote Sync
Output

Provides strobe
and normal sync for
remote NAC power
supplies

Untwisted, unshielded pair
wire

Distance set by 295
ohm resistance
limitation

12-18 AWG (3.25 - 0.75 mm

2

)

Table E.1 FACP Wire Specifications

1 When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.