1 system point, System point – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 145

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

145

Read Status

Operating Instructions

The following screens will be displayed:

4.23.1 System Point

Pressing 1 while viewing Read Status Screen #1 will cause the following screen to be displayed:

The operator selects the type of device which is to be viewed by pressing 1 for Detector or 2 for
Module. If 1 is pressed, the display will change to the following screen:

Entering the three digit detector address will cause the control panel to display the current status of
the selected device. For example, if a detector with address 001 on the SLC loop is entered, a
display similar to the following will appear:

The information in the preceding display includes:

NORMAL - the present status (could also be ALARM, TROUBL, DISABL, etc.)

SMOKE (PHOTO) - the device type which is a photoelectric smoke detector (could also be
ION for ionization smoke detector)

NORTH CLASSROOM - the Adjective/Noun label for this device

Z005 - the first of five possible assigned software zones

1D001 - 1 = SLC Loop, D = Detector, 001 = Address 001

V - Alarm Verification Enabled (V = Yes, * = No)

S - Silenceable for control modules (S = Yes, * = No)

W - Walktestable for control and monitor modules (W = Yes, * = No)

Pressing the down arrow key, while viewing the screen shown above, will allow the operator to
view additional programming information about the selected device, such as:

Enable/Disable Status

Device Type

Alarm Verification On/Off (for detectors)

Walktest Yes/No

PAS (Positive Alarm Sequence) Yes/No (for detectors only)

READ STATUS

1=SYSTEM POINT

2=ZONES

3=POWER

READ STATUS

1=TROUBLE REMINDER

2=TIMERS

3=NACS

Read Status Screen #1

Read Status Screen #3

READ STATUS

1=RELAYS

2=PROGRAM CHECK

3=HISTORY

Read Status Screen #5

READ STATUS

1=ANNUNCIATORS

2=PHONE LINE

3=CENTRAL STATION

Read Status Screen #2

READ STATUS

1=SERVICE TERMINAL

2=PRINTER/PC

3=PRINT

Read Status Screen #4

READ STATUS

1=TIME-DATE

Read Status Screen #6

READ STATUS

1=SYSTEM POINT

2=ZONES

3=POWER

Read Status Screen #1

READ SYSTEM POINT

SELECT TYPE

1=DETECTOR

2=MODULE

READ SYSTEM POINT

ENTER DETECTOR#


NORMAL SMOKE(PHOTO)

NORTH CLASSROOM

Z005

V 1D001

Advertising