MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

43

Optional Module Installation

Installation

The following formulas were used to generate the wire distance chart:

Exception: When using the ANN-RLY module, the installer must ensure that the maximum
24VDC power line drop does not exceed 0.3 volts. This results in the following wiring limitations:

Wiring Distance Calculation Example:

Suppose a system is configured with the following ANN-BUS modules:

3 ANN-80 Remote Fire Annunciators

1 ANN-S/PG Serial/Parallel Printer Interface Module

The total worst case current is calculated as follows:

Using this value and referring to the Wiring Distance Table 2.1 on page 42, it can be found that the
available options are:

926 feet maximum using 22 Gauge wire

2,344 feet maximum using 18 Gauge wire

3,731 feet maximum using 16 Gauge wire

5,906 feet maximum using 14 Gauge wire

Maximum Resistance (Ohms)

=

6.0 Volts

Total Worst Case Current Draw (amps)

Maximum Wire Length (feet)

=

Maximum Resistance (Ohms)

*500

(6,000 feet maximum)

Rpu

where: Rpu = Ohms per 1,000 feet for various Wire Gauges (see table below)

Wire Gauge

Ohms per 1,000 feet (Rpu)

22

16.2

18

6.4

16

4.02

14

2.54

Wire Gauge

Maximum Wire Length

18

312 feet

16

497 feet

14

787 feet

12

1,250 feet

ANN-80 Current Draw

= 3 X 0.040 amps

= 0.120 amps

ANN-S/PG Current Draw

= 1 X.0.040 amps

= 0.040 amps

Total Worst Case Current Draw

= 0.160 amps