Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 111

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

111

Master Programming Level

Programming

ANN-LED Options

Pressing 2 for Module Options while viewing the ANN-BUS Address Screen when the ANN-LED
option is selected, will display the following screen:

The first screen indicates that the ANN-LED at the selected ANN-BUS address is programmed to
annunciate Alarms, Supervisories, and Troubles for SLC Loop #1 addressable Detectors with
addresses 1 through 10. The programming can be changed using ANN-LED Address Screens 2
and 3.

Pressing 1 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate either Point (addressable device address) information or Zone information.

Pressing 2 while viewing ANN-LED Address Screen #2 will program the annunciator module to
annunciate only Alarms for addressable device addresses 1-30 or Alarms, Supervisories, and
Troubles for addressable device addresses 1-10.

Pressing 1 while viewing ANN-LED Address Screen #3 will select the Point or Zone range to be
annunciated - refer to the tables in “ANN-LED Zone Option - Alarm Only (for use with ANN-
RLED module)” on page 111 and “AN
N-LED Point Option - Alarm Only (for use with ANN-
RLED module)” on page 113
.

Pressing 2 while viewing ANN-LED Address Screen #3 will select either addressable detectors or
addressable modules to be annunciated.

ANN-LED Zone Option - Alarm Only (for use with ANN-RLED module)

If Zone is selected as the module option, and the module is programmed to annunciate alarms only,
the first ten LEDs on the first ANN-LED module will display the system status information. The
remaining 30 LEDs on the first module and the last 30 LEDs on the remaining modules will display
the active/alarm status of each zone in the Zone Range programmed for that particular module. The
LED assignments for each ANN-LED module will be as follows.

Alarm Silenced

NAC 1 Fault

NAC 2 Fault

NAC 3 Fault

NAC 4 Fault

Earth Fault

Battery Fault

Charger Fault

Disabled

Maintenance

Zone 00

Active/Alarm

Zone 01

Active/Alarm

Zone 02

Active/Alarm

Zone 03

Active/Alarm

Zone 04

Active/Alarm

Zone 05

Active/Alarm

Zone 06

Active/Alarm

Zone 07

Active/Alarm

Zone 08

Active/Alarm

Zone 09

Active/Alarm

Zone 10

Active/Alarm

Zone 11

Active/Alarm

Zone 12

Active/Alarm

Zone 13

Active/Alarm

Zone 14

Active/Alarm

Zone 15

Active/Alarm

Zone 16

Active/Alarm

Zone 17

Active/Alarm

Zone 18

Active Alarm

Zone 19

Active/Alarm

Zone 20

Active/Alarm

Zone 21

Active/Alarm

Zone 22

Active/Alarm

Zone 23

Active/Alarm

Zone 24

Active/Alarm

Zone 25

Active/Alarm

Zone 26

Active/Alarm

Zone 27

Active/Alarm

Zone 28

Active/Alarm

Zone 29

Active/Alarm

Table 3.2 ANN-RLED Module #1

PRIMARY ANN-BUS

1=ENABLED YES

2=MODULES INSTALLED

3=AUTO-CONFIGURE

ANN-BUS Screen #2

ANN-LED - ADDR X-1

SLC 1 DET 1-10

ALARM, TBL, SUPV

ANN-LED Address Screen #1

ANN-LED - ADDR X-1

1=POINT/ZONE

2=ALARM/ATS

ANN-LED Address Screen #2

ANN-LED - ADDR X-1

1=RANGE

2=DET/MOD

ANN-LED Address Screen #3

Advertising