MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Master Programming Level

Press the number corresponding to the module/device type that is installed with the selected
address.

If ANN-I/O, ANN-LED, or ANN-RLY is the selected module type, the following ANN-BUS
Address Screen will be displayed:

Since the options for each of these module types can be individually set, pressing 2 for Module
Options
, while viewing the ANN-BUS Address Screen will display the available options as
described below.

ANN-I/O Options

Pressing 2 for Module Options while viewing ANN-BUS Address screen when the ANN-I/O
option is selected will display the following screen:

The first screen indicates that the ANN-I/O at ANN-BUS address 1 is programmed to annunciate
SLC Loop #1 addressable Detectors with addresses 1 through 30. The programming can be
changed using ANN-I/O Address Screens 2 and 3.

Pressing 1 while viewing ANN-I/O Address Screen #2 will program the annunciator module to
annunciate either Point (addressable device address) information or Zone information.

Pressing 1 while viewing ANN-I/O Address Screen #3 will select the Point or Zone range to be
annunciated (refer to the tables in “ANN-I/O Zone Option” on page 109 and “ANN-I/O Point
Option” on page 110).

Pressing 2 while viewing ANN-I/O Address Screen #3 will select either addressable detectors or
addressable modules to be annunciated.

NOTE: If the module type selected is the ANN-80, ANN-S/PG, or ANN-ACC or if Not Installed is
selected, the ANN-BUS Address Screen shown on the previous page will be displayed following
the module selection. The options selected for each of these modules will be the same for all
modules of the same type (refer to “ANN-S/PG (Print) Options” on page 116 and “ANN-80
Options” on page 117).

ANN-BUS MODULE X-1

ANN-BUS ADDRESS

1=TYPE ANN-I/O

2=MODULE OPTIONS

ANN-BUS Address Screen

ANN-I/O - ADDR X-1

LOOP1 DET 1-30

ACTIVE LEDS ONLY

ANN-I/O Address Screen #1

ANN-I/O - ADDR X-1

1=POINT/ZONE

ANN-I/O Address Screen #2

ANN-I/O - ADDR X-1

1=RANGE

2=DET/MOD

ANN-I/O Address Screen #3