Page 42

Advertising
background image

42

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Installation

Optional Module Installation

2.9.2 ANN-BUS Annunciators/Modules

ANN-BUS Wiring

This section contains information on calculating ANN-BUS wire distances and the types of wiring
configurations (Class B).

Calculating Wiring Distance for ANN-BUS Modules

The following instructions will guide the installer in determining the type of wire and the maximum
wiring distance that can be used with FACP ANN-BUS accessory modules.

To calculate the wire gauge that must be used to connect ANN-BUS modules to the FACP, it is nec-
essary to calculate the total worst case current draw for all modules on a single 4-conductor bus.
The total worst case current draw is calculated by adding the individual worst case currents for each
module. The individual worst case values are shown in the following table:

After calculating the total worst case current draw, Table 2.1 specifies the maximum distance the
modules can be located from the FACP on a single wire run. The table ensures 6.0 volts of line
drop maximum. In general, the wire length is limited by resistance, but for heavier wire gauges,
capacitance is the limiting factor. These cases are marked in the chart with an asterisk (*). Maxi-
mum length can never be more than 6,000 feet (1,800 m), regardless of gauge used. The formula
used to generate this chart is shown in the note below.

Model Number

Worst Case Current Draw

1

1 When powering the ANN-BUS from one of the (nonresettable) DC power out-

puts at TB1, the total worst case current draw cannot exceed 1.0 amp. If
sharing this DC output with other devices, the worst case current drawn by
these devices must be combined with the ANN-BUS current draw, and the
total cannot exceed 1.0 amp. If the total current demand exceeds 1.0 amp,
refer to “Powering ANN-BUS Devices from an Auxiliary Power Supply” on
page 45
.

ANN-80(C) LCD Annunciator/Indicator

0.040 amps

ANN-S/PG Serial/Parallel Printer Interface Module

0.040 amps

ANN-I/O LED Driver Module

0.200 amps

ANN-(R)LED Annunciator Module

0.068 amps

ANN-RLY Relay Module

0.075 amps

ANN-LC Lite-Connect Module

0.150 amps

Wiring Distance: ANN-BUS Modules to FACP

Total Worst Case Current

Draw (amps)

22 Gauge

18 Gauge

16 Gauge

14 Gauge

0.100

1,852 ft.

4,688 ft.

* 6,000 ft.

*6,000 ft.

0.200

926 ft.

2,344 ft.

3,731 ft.

5,906 ft.

0.300

617 ft.

1,563 ft.

2,488 ft.

3,937 ft.

0.400

463 ft.

1,172 ft.

1,866 ft.

2,953 ft.

0.500

370 ft.

938 ft.

1,493 ft.

2,362 ft.

Table 2.1 Wiring Distances