9 medical alert condition operation, 10 mass notification operation, 11 nac operation – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 139

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

139

Medical Alert Condition Operation

Operating Instructions

4.9 Medical Alert Condition Operation

Medical alert operation is:

not intended for nurse call stations (applications) per UL1069.

not intended for signaling professional medical staff.

to be used for summoning security guards or other trained personnel within the facility

intended for Manual activation.

Medical Alert Condition operation will initiate the following events:

The piezo sounder 1/4 second On, 1/4 second Off

The LCD displays a medical alert message along with the device name, type, address,
adjective/noun, associated zones, and time/date

Communicate the medical alert condition to the Central Station

Relays programmed for medical alert will be activated

The alarm relay is not activated

Fire Alarm NACs will not activate

SLC NACs (control modules) will activate

Timers are not started

Store event in history buffer

Activate appropriate LED on the ANN-LED annunciator (required for this application)

Each ANN-LED can support up to 10 zones.

Medical alert conditions latch. They can be assigned to software zones.

4.10 Mass Notification Operation

The FACP may be installed with an ECC-50/100 audio system to provide mass notification opera-
tion. The FACP must control the ECC-50/100 via the ANN-BUS. Refer to “Automatic Audio
Panel Control” on page 61 fo
r details and wiring information.

Some mass notification installations may require that the activation of the audio system results in
an override of an active fire notification at the FACP. This is determined by a risk assessment in
accordance with the local AHJ. The FACP provides the flexibility to accommodate override or
non-override operation. For override operation, FACP NACs and/or other SLC control modules
may be deactivated while the mass notification event is active. No other FACP operation is over-
ridden or interrupted. If override operation has been selected, notification for a fire event will
resume upon termination of the mass notification event at the audio system.

When mass notification override is enabled, mass notification alarms will result in a mass notifica-
tion event being sent to the central station. An event code can also be sent indicating which mes-
sage is playing on the audio system. Message event code transmission must be enabled in
programming.

Refer to page 101 for programming mass notification override at the system level.
Refer to page 86 for programming mass notification override for SLC control modules.
Refer to page 99 for programming mass notification override for onboard NACs.
Refer to page 122 for programming message event code transmission to the central station.

4.11 NAC Operation

There are four programmable NACs (Notification Appliance Circuits) resident on the
MS-9200UDLS main circuit board. All NACs may be programmed as silenceable or
nonsilenceable and may also be programmed for steady or coded operation. Coded operation
provides a choice between March Time, Temporal or California coding.