Section 1: Product Description

The Fire-Lite MS-9200UDLS is a combination FACP (Fire Alarm Control Panel) and DACT
(Digital Alarm Communicator/Transmitter) all on one circuit board. This compact, cost effective,
intelligent addressable control panel has an extensive list of powerful features.The combination of
Fire-Lite’s newer series devices and legacy 300 Series devices, along with the MS-9200UDLS
FACP, offer the latest in fire protection technology. The power supply and all electronics are con-
tained on a single circuit board housed in a metal cabinet, providing a complete fire control system
for most applications. Optional modules, which plug into the main circuit board, are available for
special functions. Available accessories include LED, graphic and LCD annunciators, reverse
polarity/city box transmitter, local and remote upload/download software and remote power expan-
sion.

The integral DACT transmits system status (alarms, troubles, AC loss, etc.) to a Central Station via
the public switched telephone network. It also allows remote programming or interrogation of the
control panel using the PS-Tools Upload/Download utility via the public switched telephone net-
work. Local programming and interrogation is also possible using the PS-Tools and the USB port
(J12) on the FACP. Any personal computer with WINDOWS

®

XP or greater, and compatible

modem with a speed of 2400 baud or faster and PS-Tools software may serve as a Service Termi-
nal. This allows download of the entire program or upload of the entire program, history file, walk-
test data, current status and system voltages.

Inventory

When MS-9200UDLS shipment is received, check that all parts have been included in shipment.
The MS-9200UDLS shipment consists of one of each of the following:

main circuit board with display

backbox with door

plastic bag containing screws, cables, key, etc.

manual

1.1 Features and Options

Automated activation of the ECC-50/100 Emergency Command Center

ECC-FFT Firefighter Telephone option

LiteSpeed™ polling protocol for faster SLC response time

SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with twisted, unshielded wire
(refer to “Wire Requirements” on page 177)

Built-in DACT (Digital Alarm Communicator/Transmitter)

Single addressable SLC loop which meets NFPA Style 4, 6 and 7 requirements

198 addressable device capacity (99 detectors and 99 control/relay/monitor modules)

99 software zones

Four (4) Style Y (Class B) NACs (Notification Appliance Circuits) with the option to convert
to four (4) Style Z (Class A) circuits - special application power

3.0 amps total 24 VDC output circuit current, expandable to 6.0 amps with optional
transformer

Two programmable relay outputs and one fixed trouble relay

Synchronization output for remote power supply applications (special application)

Built-in Programmer

NOTE: MS-9200UDLS is used in this manual to refer to both the MS-9200UDLS/C (120 VAC
versions) and the MS-9200UDLSE (240 VAC version) FACPs.