3 300 series intelligent addressable devices, 4 addressable device accessories, End-of-line resistor assembly – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 20: Power supervision relay, Eol-c(r/w) mounting plate, 6 optional modules, 7 accessories, 1 ps-tools programming utility, Optional modules 1.7: accessories, Ps-tools programming utility

Advertising
background image

20

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Product Description

Optional Modules

1.5.3 300 Series Intelligent Addressable Devices

Fire-Lite’s 300 Series Intelligent Addressable Devices are fully compatible with the MS-
9200UDLS FACP. The address of 300 Series devices cannot be set above 99. Refer to the SLC
Wiring Manual for a list of compatible addressable devices.

1.5.4 Addressable Device Accessories

End-of-Line Resistor Assembly

The End-of-Line resistors are included with each module. Refer to the specific module documenta-
tion for specific information.

Power Supervision Relay

The UL listed End-of-Line power supervision relay is used to supervise the power to 4-wire smoke
detectors and notification appliances.

EOL-C(R/W) Mounting Plate

The EOL-CR (red) and EOL-CW (white) are single End-of-Line resistor plates which are required
for use in Canada. An ELR, which is supplied with each module and fire alarm control panel, is
mounted to the EOL-C(R/W) plate. Resistors mounted to the plate can be used for the supervision
of a monitor and control module circuit.

1.6 Optional Modules

The MS-9200UDLS main circuit board includes option module connectors for the following
modules:

4XTMF Transmitter Module

The 4XTMF provides a supervised output for local energy municipal box transmitter, alarm and
trouble reverse polarity. It includes a disable switch and disable trouble LED. A jumper on the
module is used to select an option which allows the reverse polarity circuit to open with a system
trouble condition if no alarm condition exists. The module plugs into connectors J5 and J6 which
are located near the right edge the main circuit board. When the 4XTMF module is installed,
Jumper JP3, on the main circuit board, must be cut to allow supervision of the module.

ZNAC-92 Class A Converter Module

The ZNAC-92 is an optional Class A conversion module which mounts to connector J14 on the
upper left side of the MS-9200UDLS circuit board. This module allows the MS-9200UDLS to sup-
port four (4) Style Z (Class A) Notification Appliance Circuits.

1.7 Accessories

1.7.1 PS-Tools Programming Utility

The PS-Tools Programming Utility can be used to locally or remotely program the FACP from
most IBM compatible computers (PC), running Windows

®

XP (or newer). The FACP program

files can also be created and stored on the PC for future download to the control panel. The PK-CD
Kit includes the Windows-based Programming Utility software on CD-ROM with on-line help file.
A standard USB cable with male-A to male-B connectors, which must be purchased separately, is
required for local connection of the PC to the USB port J12 on the FACP main circuit board.
Remote programming requires that the PC have a 2400 baud (or faster) modem.

Advertising