Calculating the System Current Load

Power Supply Calculations

Table 7.3 contains columns for calculating current load. For each column, calculate the current and
enter the total (in amperes) in the bottom row. When finished, copy the totals from Calculation
Column 2 and Calculation Column 3 to Table 7.4 on page 162. For maximum output current
available per circuit and per panel, refer to Section 1.2, “Specifications”, on page 15.

Device Type

Calculation Column 1

Primary (AC) Power Source

Fire Alarm Current (amps)

Calculation Column 2

Secondary (Battery) Power Source

Fire Alarm Current (amps)

Calculation Column 3

Secondary (Battery) Power Source

Standby Current (amps)

Qty

X[current draw]=

Total

Qty

X[current draw]=

Total

Qty

X[current draw]=

Total

Main Circuit Board

1

X[0.275]=

0.275

1

X[0.145]=

0.145

ANN-80(C)

[ ]

X[0.040]=

[ ]

X[0.040]=

[ ]

X[0.015]=

ANN-(R)LED

[ ]

X[0.068]=

[ ]

X[0.068]=

[ ]

X[0.028]=

ANN-RLY

[ ]

X[0.075]=

[ ]

X[0.075]=

[ ]

X[0.015]=

ANN-I/O

[ ]

X[0.200]=

[ ]

X[0.200]=

[ ]

X[0.035]=

ANN-S/PG

[ ]

X[0.045]=

[ ]

X[0.045]=

[ ]

X[0.045]=

ANN-LC

[ ]

X[0.150]=

[ ]

X[0.150]=

[ ]

X[0.150]=

ACM-8RF

[ ]

X[0.158]

1

=

[ ]

X[0.158]=

[ ]

X[0.030]=

ACM-16ATF

ACM-32AF

[ ]

X[0.056]

2

=

[ ]

X[0.056]=

[ ]

X[0.040]=

AEM-16ATF

AEM-32AF

[ ]

X[0.018]

2

=

[ ]

X[0.018]=

[ ]

X[0.002]=

AFM-16ATF

AFM-32AF

[ ]

X[0.056]

2

=

[ ]

X[0.056]=

[ ]

X[0.040]=

AFM-16AF

[ ]

X[0.065]

2

=

[ ]

X[0.065]=

[ ]

X[0.025]=

LDM-32F

[ ]

X[0.056]

3

=

[ ]

X[0.056]=

[ ]

X[0.040]=

LDM-E32F

[ ]

X[0.018]=

[ ]

X[0.018]=

[ ]

X[0.002]=

LCD-80F

[ ]

X[0.064]=

[ ]

X[0.064]=

[ ]

X[0.025]=

ECC-FFT

N/A

[ ]

X[0.230]=

[ ]

X[0.120]=

4XTMF

[ ]

X[0.011]

4

=

[ ]

X[0.011]=

[ ]

X[0.005]=

4-wire Detector Heads

[ ]

X[ ]=

[ ]

X[ ]

5

=

[ ]

X[ ]=

Power Supervision

Relays

6

[ ]

X[0.025]=

[ ]

X[0.025]=

[ ]

X[0.025]=

CP350 & CP355

maximum alarm draw

for all devices =

0.400

maximum alarm draw

for all devices =

0.400

[ ]

X[0.00030]=

SD350 & SD355

[ ]

X[0.00030]=

SD350T & SD355T

[ ]

X[0.00030]=

AD350 & AD355

[ ]

X[0.00030]=

H350 & H355

[ ]

X[0.00030]=

H350R & H355R

[ ]

X[0.00030]=

H355HT

[ ]

X[0.00030]=

D350P & D350PL

[ ]

X[0.00030]=

D350RP & D350RPL

[ ]

X[0.00030]=

B501BH & B501BHT

7

[ ]

X[0.001]=

B224RB Relay Base

[ ]

X[0.00050]=

B224BI Isolator Base

[ ]

X[0.00045]=

MMF-300

[ ]

X[0.00040]=

MMF-300-10

[ ]

X[0.00350]=

MDF-300

[ ]

X[0.00075]=

MMF-301

[ ]

X[0.000375]=

MMF-302

[ ]

X[0.00027]=

MMF-302-6

[ ]

X[0.00200]=

BG-12LX

[ ]

X[0.00030]=

CMF-300

[ ]

X[0.00039]=

CMF-300-6

[ ]

X[0.00225]=

CRF-300

[ ]

X[0.00027]=

CRF-300-6

[ ]

X[0.00145]=

I300

[ ]

X[0.00040]=

NAC #1

[ ]

X[ ]=

[ ]

X[ ]=

NAC #2

[ ]

X[ ]=

[ ]

X[ ]=

NAC #3

[ ]

X[ ]=

[ ]

X[ ]=

NAC #4

[ ]

X[ ]=

[ ]

X[ ]=

FCPS (remote sync)

[ ]

X[0.02]=

[ ]

X[0.0217]=

Current Draw from TB3

[ ]

[ ]=

[ ]

[ ]=

[ ]

[ ]=

Sum each column for

totals

AC Powered,
Fire Alarm Load

8

=

Battery Powered,
Fire Alarm Load =

Battery Powered,
Standby Load =

Table 7.3 System Current Load Calculations

1 All eight ACM-8RF relays activated on a single module.
2 All annunciator LEDs on
3 LDM-32F or ANN-I/O with LEDs on
4 If using the Reverse Polarity Alarm output, add 0.005 amps; if using the Reverse Polarity Trouble output, add another

0.005 amps.

5 Refer to the Device Compatibility Document for standby current.
6 Must use compatible listed Power Supervision Relay.
7 Maximum alarm current for each sounder base is 0.015 amps which must be supplied by aux. 24VDC source.
8 Total current load cannot exceed 3.0 amps with one transformer or 6.0 amps with optional XRM-24B(E) added.