MBT-1 Municipal Box Trip - Silenceable

NFPA Standard-Specific Requirements

C.2 MBT-1 Municipal Box Trip - Silenceable

The following figure illustrates the connection of the MBT-1 (Municipal Box Trip) between the
FACP and a Local Energy Municipal Box. The use of an addressable control module programmed
for General Alarm and Silenceable allows silencing of the Municipal Box without resetting the
panel or box.

FIRE

T11

T10
T9

T8
T7

T6

T1

T2

T3
T4

T5

+ 24V -

NON-RST

POWER

+ 24V -

RST

POWER

REMOTE PWR
SUPPLY SYNC

+ -

1B+ 3B+ 3B- 1B-

2B+ 4B+ 4B- 2B-

NO NC C

NO NC C

NC NO C

TB5

TB3

TB7

TB2

TB1

TB4

TB9

TB8

TB6

TB10

JP7

Xmt Rcv Dtr Gnd
A B
In+ In- Out+ Out-

+ -
A B

B+ A+ B- A- A B
Slc Slc Slc Slc Shield

FACP Main Circuit Board

CMF-300

Control Module*

24 VDC, Nonresettable

+ -

SLC Loop

B

+

-

B

Shield

red

black

MBT-1

brown wire

white wire

EOLR-1 Power
Supervision Rela
y

Alarm polarity shown!

-
+

- To next device
+ on SLC Loop
Braided-shield/Drain Wire

The addressable Control Module must be programmed
as Silenceable and General Alarm.

Gamewell Model M34-56
Local Energy Municipal Box

Note: 10

maximum loop

resistance due to wiring from
power supply to Municipal Box.

Connect wires to two
red terminals on box.

(All contacts shown in energized position).

Figure C.5 MBT-1 Silenceable

9

2

u

d

ls

c

-M

B

T

1

n

e

w

.w

m

f

*If the SLC device does not match the one in this figure, refer to the SLC manual wiring conversion
charts for legacy and newer versions of the modules.