2 specifications, Specifications – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 15

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

15

Specifications

Product Description

ANN-RLED Annunciator Module annunciates alarms only

ANN-LC Lite-Connect Module

Automated activation of the ACC-25/50(ZS/T) Audio-Command-Center

Legacy ACS/TERM Annunciators (cannot be used if ANN annunciators are used):

ACS Series-LED Zone Annunciators

LDM Graphic Annunciator Series

LCD-80F Liquid Crystal Display point annunciator

LCD-80FC Remote Fire Indicator (Canadian applications)

ACM-8RF Relay Module

1.2 Specifications

Refer to Illustration on page 10 for terminal locations and connections.

AC Power - TB11

MS-9200UDLS: 120 VAC, 60 Hz, 2.0 amps
MS-9200UDLSE: 220/240 VAC, 50 Hz, 1.2 amps
Wire size: minimum 14 AWG (2.00 mm

2

) with 600 V insulation

Battery (Sealed Lead Acid Only) - J9

Maximum Charging Circuit: Normal Flat Charge – 27.6 VDC @ 1.4 amps
Maximum Battery Charger Capacity: 18 Amp Hour (FACP cabinet holds maximum of two 18 Amp
Hour batteries. The BB-26 Battery Box holds two 26 Amp Hour batteries and the CHG-75. For
greater than 26 Amp Hour up to 120 Amp Hour batteries, use the CHG-75 or CHG-120F Battery
Charger and BB-55F Battery Box).
Minimum Battery Size: 7 Amp Hour
Note: Jumper JP5, on the FACP main circuit board, must be cut to disable the FACP battery charger
when using an external battery charger.

Communication Loop - TB10

24 VDC nominal, 27.6 VDC maximum
Maximum length - refer to “Wire Requirements” on page 177)
Maximum loop current is 400 mA (short circuit) or 100 mA (normal)
Maximum loop resistance is 40 ohms
Supervised and power-limited circuit
Refer to SLC Loop manual for wiring information

Notification Appliance Circuits - TB3 & TB4

Four (4) Style Y (Class B) NAC circuits, which can be converted to four (4) Style Z (Class A)
circuits with optional ZNAC-92 converter module
Special Application full-wave rectified power
Power-limited circuitry
NAC wiring requirements refer to “NAC Wiring” on page 179
Nominal operating voltage: 24 VDC
Current-limit: fuseless, electronic, power-limited circuitry
Maximum signaling current per circuit: 2.5 amps (see Figure 1.1 on page 17)
End-of-Line Resistor: 4.7 k

, ½ watt (P/N 71252 UL listed) required for each circuit

Refer to the Device Compatibility Document for listed compatible devices

Two Programmable Relays and One Fixed Trouble Relay - TB5, TB6 & TB7

Contact rating: 2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive)
Form-C relays
Refer to Figure 2.7 on page 33 for information on power-limited relay circuit wiring