Master Programming Level

Programming

Pressing 3 for Parity while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allows the user to select between No Parity, Even Parity, or Odd Parity.

Pressing 1 for Stop Bits while viewing ANN-S/PG Options screen #3 will cause a screen to appear
which allows the user to select between 1.0 or 2.0 Stop Bits.

ANN-LED Options

This option allows the programmer to configure the optional ANN-LED annunciator. Pressing 2
while viewing the ANN-BUS screen will display the following screens.

The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-LED module will ever sound. Pressing 1 while viewing the ANN-LED Options
Screen causes the display to toggle between Piezo Enable Yes and Piezo Enable No.

The Lamp Test Enable (LMP TST ENABLE) option allows the programmer to select whether the
Lamp Test button on any installed ANN-LED annunciator will function normally or always be
ignored. Pressing 2 while viewing the ANN-LED Options Screen causes the display to toggle
between Lmp Tst Enable Yes (Lamp Test button functions normally) and Lmp Tst Enable No (Lamp
Test button never functions).

The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the
Silence button on any installed ANN-LED annunciator will function normally or always be
ignored. Pressing 3 while viewing the ANN-LED Options Screen causes the display to toggle
between Sil Btn Enable Yes (Silence button functions normally) and Sil Btn Enable No (Silence
button never functions).

ANN-80 Options

Pressing 3 while viewing the ANN-BUS screen will display the following screen:

The Piezo Enable option allows the programmer to select whether the piezo sounder on any
installed ANN-80 module will ever sound. Pressing 1 while viewing the ANN-80 Options Screen
#1 causes the display to toggle between Piezo Enable Yes and Piezo Enable No.

The Lock Enable option allows the programmer to select whether or not any installed ANN-80
annunciator must be unlocked by its key before any annunciator key presses will function. Pressing
2 while viewing the ANN-80 Options Screen #1 causes the display to toggle between Lock Enable
Yes
(annunciator must be unlocked for keys to function) and Lock Enable No (lock position is
ignored).

The Acknowledge Button Enable (ACK BTN ENABLE) option allows the programmer to select
whether the Ack/Step button on any installed ANN-80 annunciator will function normally or
always be ignored. Pressing 3 while viewing the ANN-80 Options Screen #1 causes the display to
toggle between Ack Btn Enable Yes (Ack/Step button functions normally) and Ack Btn Enable No
(Ack/Step button never functions).

The Silence Button Enable (SIL BTN ENABLE) option allows the programmer to select whether the
Silence button on any installed ANN-80 annunciator will function normally or always be ignored.
Pressing 1 while viewing the ANN-80 Options Screen #2 causes the display to toggle between Sil
Btn Enable Yes
(Silence button functions normally) and Sil Btn Enable No (Silence button never
functions).

ANN-BUS

1=ANN-S/PG OPTIONS

2=ANN-LED OPTIONS

3=ANN-80 OPTIONS

ANN-BUS Select Screen

ANN-LED OPTIONS

1=PIEZO ENABLE

2=LMP TST ENABLE

3=SIL BTN ENABLE

ANN-LED Options Screen

ANN-BUS

1=ANN-S/PG OPTIONS

2=ANN-LED OPTIONS

3=ANN-80 OPTIONS

ANN-BUS Screen

ANN-80 OPTIONS

1=PIEZO ENABLE

2=LOCK ENABLE

3=ACK BTN ENABLE

ANN-80 Options Screen #1

ANN-80 OPTIONS

1=SIL BTN ENABLE

2=RST BTN ENABLE

3=DRL BTN ENABLE

ANN-80 Options Screen #2

Advertising