Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 132

Advertising
background image

132

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Maintenance Programming Level

Pressing 1 while viewing Zone Setup screen will display the following screen:

A flashing cursor appears to the right of the Z. To enable a zone, enter the two digit zone number
(00 - 99). After the second digit is entered, the zone will be enabled and the cursor will return to the
original position. The next zone to be enabled can then be entered. Press Esc (Escape) to return to
the previous screen.

Pressing 2 while viewing Zone Setup screen will display the following screen:

A flashing cursor appears to the right of the Z. To disable a zone, enter the two digit zone number
(00 - 99). After the second digit is entered, the zone will be disabled and the cursor will return to
the original position. The next zone to be disabled can then be entered. Press Esc (Escape) to
return to the previous screen.

Pressing 3 while viewing Zone Setup screen will display the following screen:

Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose
applications. In the above illustration, the three zones are shown Off, which means they can be
programmed to function in the same manner as all other zones, by assigning them to input and
output devices in the Programming Zone Assignment Screen.

Pressing 1 will cause the display to change to PAS 97 On. Each press of the 1 key will cause the
display to toggle between PAS 97 On and PAS 97 Off. When Zone 97 is programmed On, a PAS
(Positive Alarm Sequence) activation of any smoke detector will cause Zone 97 to activate. By
assigning Zone 97 to a control module in the Programming Zone Assignment Screen, an output
device connected to the control module can be used to indicate a PAS condition in the control
panel. Do not assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a
PAS condition.

Pressing 2 will cause the display to change to Pre-signal 98 On. Each press of the 2 key will cause
the display to toggle between Pre-signal 98 On and Pre-signal 98 Off. When Zone 98 is
programmed On, a Pre-signal activation of any device will cause Zone 98 to activate. By assigning
Zone 98 to a control module in the Programming Zone Assignment Screen, an output device
connected to the control module can be used to indicate a Pre-signal condition in the control panel.
Do not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-
signal condition.

Pressing 3 will cause the display to change to Two Stage 99 On. Each press of the 3 key will cause
the display to toggle between Two Stage 99 On and Two Stage 99 Off. Refer to “Two Stage
Operation” on page 98
for a description of this feature.

ZONE TO ENABLE

Z

Enable Screen

ZONE TO DISABLE

Z

Disable Screen

SPEC PURPOSE ZONE

1=PAS 97 OFF

2=PRE-SIGNAL 98 OFF

3=TWO STAGE 99 OFF

Disable Screen

Advertising