Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 116

Advertising
background image

116

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

Programming

Master Programming Level

Auto-Configure

The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed
ANN-BUS modules online on the selected ANN-BUS. The software will search the selected
circuit for all ANN-BUS modules and automatically program the device type and address into the
system. For the Auto-Configure to work, the selected ANN-BUS must be enabled, the
annunciators must be connected/powered, and a unique address must be set on each annunciator.
Pressing 3 while viewing ANN-BUS Screen #1 will begin the Auto-Configure process and cause
the following screen to be displayed:

ANN-BUS

Pressing 3 for ANN-BUS Options, while viewing the ANN-BUS Select screen, will display the
following screen.

ANN-S/PG (Print) Options

The Print option allows the programmer to configure the optional printer. Pressing 1 while viewing
the ANN-BUS screen will display the following screens:

Pressing 1 for Port while viewing ANN-S/PG Options screen #1 will allow the programmer to
select between a Parallel and Serial Port for printer connection. Each press of the 1 key will cause
the display to toggle between Port PAR (parallel) and Port SER (serial). It is important to note that
the interface selected determines which options are available to the user.

If the Parallel Port option is selected, the user has the option to supervise the printer and select an
offline timer for the supervision by pressing 2 for Printer Supervision while viewing Print Options
screen #1. Each press of the 2 key will cause the display to toggle between Printer Supv NO for no
supervision and Printer Supv YES for printer supervision. Note that this option is not selectable if
the Serial Port option has been selected.

If the Parallel Port option is selected, the user has the ability to select an Offline Timer by pressing
3 while viewing Print Options screen #1. The resultant screen allows the programmer to program
the Offline Timer for a delay of between 0 and 255 seconds before loss of printer supervision is
reported as a trouble.

If the Serial Port option is selected, the Printer Supv and Offline Timer options will not be available.
The Baud Rate, Data Bits, Parity and Stop Bits options are only available when the Serial Port
option has been selected.

Pressing 1 for Baud Rate while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allow the user to select a Baud Rate of 19200, 9600, or 2400.

Pressing 2 for Data Bits while viewing ANN-S/PG Options screen #2 will cause a screen to appear
which allows the user to select 7 or 8 Data Bits.

[SELECTED] ANN-BUS

1=ENABLED YES

2=MODULES INSTALLED

3=AUTO-CONFIGURE

ANN-BUS Screen #2

ANN-BUS

AUTO-CONGFIGURE

IN PROGRESS

PLEASE WAIT

Auto-Configure Screen

ANN-BUS SELECT

1=PRIMARY

2=SECONDARY

3=ANN-BUS OPTIONS

ANN-BUS Select Screen

ANN-BUS

1=ANN-S/PG OPTIONS

2=ANN-LED OPTIONS

3=ANN-80 OPTIONS

ANN-BUS Options Screen

ANN-BUS

1=ANN-S/PG OPTIONS

2=ANN-LED OPTIONS

3=ANN-80 OPTIONS

ANN-BUS Screen

ANN-S/PG OPTIONS

1=PORT PAR

2=PRINTER SUPV NO

3=OFFLINE TIMER 60

ANN-S/PG Options Screen #1

ANN-S/PG OPTIONS

1=BAUD RATE N/A

2=DATA BITS N/A

3=PARITY N/A

ANN-S/PG Options Screen #2

ANN-S/PG OPTIONS

1=STOP BITS N/A

ANN-S/PG Options Screen #3

Advertising