MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

171

NFPA Standard-Specific Requirements

NFPA 72 Auxiliary Fire Alarm System

All connections are power-limited and supervised. This application is not suitable for separate
transmission of sprinkler supervisory or trouble conditions.

Notes:

1.

3 ohms maximum loop resistance allowed for wiring from control panel to Municipal Box.

2.

Cut JP3 on the MS-9200UDLS main circuit board to supervise placement of 4XTMF module
and circuit.

3.

Cut JP2 on the MS-9200UDLS main circuit board to enable FACP Supervisory relay.

4.

Refer to “4XTMF Transmitter Module Installation” on page 39 for detailed information.

FIRE

Gamewell Model M34-56 Local

Energy Municipal Box

Polarities shown in alarm condition

+

Nonpower-limited

Municipal Box
Circuit

+

-

-

4XTMF

Figure C.1 Municipal Box Connected to 4XTMF Transmitter Module