Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 115

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

115

Master Programming Level

Programming

The LED assignments for the modules annunciating Point Ranges 21 - 30, 31 - 40 and 41 - 50, 51 -
60, 61 - 70, 71 - 80, 81 - 90 and 91 - 99, will follow the same pattern as the second ANN-LED
Module.

ANN-RLY Options

Pressing 2 for Module Options while viewing the ANN-BUS Address Screen when the ANN-RLY
option is selected, will cause the following screen to be displayed:

The ANN-RLY module provides ten Form-C relays which can be programmed for various
functions. The initial screen displays Relays 1 through 3. Pressing the down arrow key will
display the remaining relays for this module.

To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen,
press the number key corresponding to the relay to be programmed. Following is a list of the
available programming options for each relay:

Alarm

Supervisory

Supervisory AR

Trouble

Comm Fail

Process Mon

Process Mon AR

AC Loss

Hazard

Medical

Silenceable Alarm

Zone Active XX

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Not Used

Point 11

Active/Alarm

Point 12

Active/Alarm

Point 13

Active/Alarm

Point 14

Active/Alarm

Point 15

Active/Alarm

Point 11

Trouble

Point 12

Trouble

Point 13

Trouble

Point 14

Trouble

Point 15

Trouble

Point 11

Supervisory

Point 12

Supervisory

Point 13

Supervisory

Point 14

Supervisory

Point 15

Supervisory

Point 16

Active/Alarm

Point 17

Active/Alarm

Point 18

Active/Alarm

Point 19

Active/Alarm

Point 20

Active/Alarm

Point 16

Trouble

Point 17

Trouble

Point 18

Trouble

Point 19

Trouble

Point 20

Trouble

Point 16

Supervisory

Point 17

Supervisory

Point 18

Supervisory

Point 19

Supervisory

Point 20

Supervisory

Table 3.9 ANN-LED Module #2 (Point Range 11 - 20)

PRIMARY ANN-BUS

1=ENABLED YES

2=MODULES INSTALLED

3=AUTO-CONFIGURE

ANN-BUS Screen #2

ANN-RLY - ADDR. X-1

1=RLY 1 ZONE 00

2=RLY 2 ZONE 01

3=RLY 3 ZONE 02

ANN-RLY Options Screen

Advertising