Walktest, Pre-signal, Walktest pas pre-signal – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 71

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

71

Master Programming Level

Programming

Walktest

The Walktest feature allows one person to test the system devices without the necessity of manually
resetting the control panel after each device activation. To enable a device for the Walktest feature,
press 1 while viewing the Edit Detector Screen #3 until the display reads Walktest Yes. Each press
of the 1 key will cause the display to toggle between Walktest Yes and Walktest No. Refer to
“Walktest” on page 144.

PAS

The PAS (Positive Alarm Sequence) option will program the detector to delay panel activation
(including alarm relay and communicator) for a period of 15 seconds plus a programmable time of
up to 3 minutes. Zone 97, however, will activate immediately and may be used to connect a
signaling device to indicate PAS activation (do not use a Notification Appliance Circuit for this
purpose)
. To enable the PAS feature, press 2 while viewing the Edit Detector Screen #3 until the
display reads PAS Yes. Each press of the 2 key will cause the display to toggle between PAS Yes and
PAS No. Refer to “Positive Alarm Sequence” on page 142.

For example, if a detector with address 005 is to be configured for PAS operation:

Select PAS Yes when editing the detector set to address 005

Program the desired zone or zones to be activated by this detector, in this example Z001

Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001

Program an output, such as a control module, for PAS activation by assigning zone Z97 to it.
This control module may be connected to a signaling device used to indicate a PAS
condition (do not use a Notification Appliance Circuit for this purpose)

Enable zones Z001 and Special Purpose Zone PAS 97 and set the PAS delay timer to some
value

With the preceding program settings, when the detector with address 005 is activated, zone Z97
will cause its associated control module to activate immediately, sounding the connected PAS
signaling device. Following the PAS delay time, zone Z001 will cause its associated control
module to activate and the control panel will initiate an alarm condition.

Note that a detector can be enabled for either PAS or Pre-signal but not both

Pre-signal

The Pre-signal option programs the detector to delay panel activation for a preprogrammed time
delay of up to three minutes while allowing for visual verification by a person. Note that the alarm
relay and communicator will respond to the initial alarm immediately. In addition, Zone 98 will
activate. This zone can be programmed to a control module which may be used to activate a
sounder or indicator which the installer designates as a Presignal indication (do not use a
Notification Appliance Circuit for this purpose)
. To enable the Pre-signal feature, press 3 while
viewing Edit Detector Screen #3 until the display reads Pre-signal Yes. Each press of the 3 key will
cause the display to toggle between Pre-signal Yes and Pre-signal No. Refer to “Presignal” on
page 141.Q

For example, if a detector with address 005 is to be configured for Pre-Signal operation:

Select Pre-signal Yes when editing the detector set to address 005

Program the desired zone or zones to be activated by this detector, in this example Z001

Program an output, such as a control module that is to be activated by detector 005 by
assigning the same zone to it; in this example Z001

Program an output, such as a control module, for Pre-signal activation by assigning zone
Z98 to it. This control module may be connected to a signaling device used to indicate a
Pre-signal condition (do not use a Notification Appliance Circuit for this purpose)

Enable zones Z001 and Special Purpose Zone Pre-signal 98 and set the Pre-signal delay
timer to some value

EDIT DETECTOR

1=WALKTEST

2=PAS

3=PRE-SIGNAL

Edit Detector Screen #3

EDIT DETECTOR

1=WALKTEST

2=PAS

3=PRE-SIGNAL

Edit Detector Screen #3