Ann-bus device addressing, Primary ann-bus – Fire-Lite MS-9200UDLSC Addressable Fire Alarm Control Panel User Manual

Page 45

Advertising
background image

MS-9200UDLS Series Manual — P/N 52750:H 4/14/2014

45

Optional Module Installation

Installation

Powering ANN-BUS Devices from an Auxiliary Power Supply

Figure 2.20 illustrates the powering of ANN-BUS devices from an auxiliary power supply such as
the FCPS-24FS6/8, when the total ANN-BUS power requirements exceed the panel’s DC Power
Output capability.

ANN-BUS Device Addressing

Each ANN-BUS device requires a unique address (ID Number) in order to communicate with the
FACP. A 5-position DIP switch on each device is used to set this address. The address set for these
devices must also be programmed at the FACP for the specific device (refer to the programming
section titled “ANN-BUS Options” on page 107).

A maximum of 8 devices can be connected to each FACP ANN-BUS communication circuit.
Device addresses do not need to be sequential and can be set to any number between 01 and 08.
This applies to both ANN-BUS communication circuits. Note that 00 is not a valid address. The
following table shows the DIP switch setting for each address.

When installed and enabled through FACP programming, the ANN-LC will always be set to
address 08. No dip switch settings are used to set the address on the ANN-LC.

TB1

B A (+) (-)

4 3 2 1

1 2 3 4 5 6 7 8

O N

SW1

TB4

JP3

J3

TB5

TB2

JP1

JP2

OUT4

- NAC4 +

OUT3

- NAC3 +

OUT2

- NAC2 +

OUT1

- NAC1 +

8 7 6 5 4 3 2 1

3 2 1

10

9

8

7

6

5

4

3

2

1

AUX -

IN2-

IN2+

OUT1-

OUT1+

IN1-

IN1+

SYNC IN -

SYNC IN +

AUX +

NO

NC

AUX TBL

COM

B+ A+ B- A- A B

ANN
ACS

SHIELD

SLC

SLC

SLC

SLC

TB9

TB10

A B

+ -

+ 24V -

NON-RST

POWER

+ 24V -

RST

POWER

TB1

JP7

1
2

3

-

REMOTE PWR
SUPPLY SYNC

+ -

TB2

Figure 2.20 Powering ANN-BUS Devices from FCPS-24FS6/8

ANN-80

MS-9200UDLS

FCPS-24FS6/8

-24 VDC

+24 VDC

nonresettable

Cut Ground Fault Detection jumper JP1
(FACP monitors for ground faults).

ANN-BUS and power wiring are

supervised and power-limited

9

2

u

d

b

ls

C

to

fc

p

s

to

a

n

n

.w

m

f

Primary ANN-BUS

NOTE: Address (ID Number) DIP switches on some devices may have more than 5 switch
positions. Unless otherwise specified in the documentation supplied with each device, switch
positions 6 and above must be set to OFF.